User Guide

M9102-AGA-3S and M9104-xGA-3S Series Electric Non-Spring Return Actuators Installation Instructions4
Wiring
M9102-AGA-3S, M9104-AGA-3S
The M9102 and M9104 Series Electric Non-Spring
Return Actuators require an AC 24 V input signal and
are compatible with a variety of VAV and VVT
controllers. These electric actuators include M3 screw
terminals. See Figure 7 and Figure 8 for proper wiring.
Note: When using an AGA model, you must use a
VAV or VVT controller and/or software that provides a
timeout function at the end of rotation (stall) to avoid
excessive wear or drive time on the actuator motor.
M9104-IGA-3S
The M9104-IGA Series Electric Non-Spring Return
valve actuators require an AC 24 V input signal and
work with a variety of controllers. These electric
actuators include M3 screw terminals and have an
auto-shutoff feature to prevent excessive wear or drive
time on the motor. See Figure 9 and Figure 10 for
proper wiring options.
Figure 7: M9102-AGA-3S Control Wiring
Diagram
~
~
~
AC 24 V 50/60 Hz
2
1
3
F
I
G
:
M
9
1
0
2
-
A
G
A
-
3
S
d
i
a
g
Figure 8: M9104-AGA-3S Control Wiring
Diagram
~~
AC 24 V 50/60 Hz
321
~
Figure 9: M9104-IGA-3S Control Wiring
Diagram - Floating
~~
AC 24 V 50/60 Hz
3
~
12
Figure 10: M9104-IGA-3S Control Wiring
Diagram - On/Off
~~
AC 24 V 50/60 Hz
312
~