Install Instructions

M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 3
Note: To change the rotation range on:
-xGC models with auxiliary switches,
one or both of the switches may need
adjustment. See the Auxiliary
Switches (xGC Models) section.
-HGx models with zero and span
potentiometers, adjust both
potentiometers. See the
Potentiometers (HGx Models) section.
Feedback Signal
For AGD and AGE models, resistance feedback is
reduced corresponding to the reduced rotation range.
For the GGx, HGx, and JGx models, changing the
rotation range changes the feedback signal and the
operating range proportionally. (See Figure 4.)
Direct or
Reverse
Acting
Reverse
Acting
(RA)
Direct
Acting
(DA)
135 0 23 45 68 90 113
0-135 ohms
Feedback
1000 0 167 333 500 667 833
0-1000 ohms
Feedback
0.0 V 10.0 V8.3 V6.7 V5.0 V3.3 V1.7 V
0-10 V
Feedback
10.0 V8.7 V7.3 V6.0 V4.7 V3.3 V2.0 V
2-10 V
Feedback
10.0 V 0.0 V1.7 V3.3 V5.0 V6.7 V8.3 V
0-10 V
Feedback
10.0 V 2.0 V3.3 V4.7 V6.0 V7.3 V8.7 V
2-10 V
Feedback
Note: 0 to 10 V or 2 to 10 V feedback is available on all GGx, HGx,
and JGx models, 0 to 135 ohms feedback is available on AGD
models, and 0 to 1000 ohms feedback is available on AGE models.
75°60°45°30°15° 90°
Coupler Adjustment
45°
30°60°
90°
75° 15°
Rotation Range
Figure 4: Nominal Feedback Signal Relative to the
Rotation Range
Wiring
!
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making
electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge
électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all
wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
the equipment.
MISE EN GARDE : Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir
vérifié tous les raccords de câblage. Des fils formant
un court-circuit ou connectés de façon incorrecte
risquent d'endommager irrémédiablement
l'équipement.
IMPORTANT: Make all wiring connections in
accordance with local, national, or regional
regulations.