Submittal Sheet
4 M9108 Series Proportional Electric Non-spring Return Actuators Submittal Bulletin
Technical Specifications
Product
M9108 Series Proportional Electric Non-spring Return Actuators
Power Requirements
20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 7.5 VA supply, Class 2
Input Signal
0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA
Input Signal Adjustments
Jumper Selectable: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA
Adjustable: Zero, 0 to 6 VDC, 0 to 12 VDC, or 0 to 12 mA
Span, 2 to 10 VDC, 4 to 20 VDC, or 4 to 20 mA
Factory Setting: 0 to 10 VDC, 0 to 20 mA, CW rotation with signal increase
Action is jumper selectable Direct (CW) or Reverse (CCW) with
signal increase
Input Impedance
Voltage Input, 205,000 ohms for 0 (2) to 10 V and 410,000 ohms for 0 (4) to 20 V
Current Input, 500 ohms
Feedback Signal
0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA)
Corresponds to input input signal span selection
Auxiliary Switch Rating
xGC: Two Single-Pole, Double-Throw (SPDT) switches rated at 24 VAC
1.5 A inductive, 3.0 A resistive; 35 VA maximum per switch, Class 2
Mechanical Output
(Running Torque)
70 lb∙in (8 N∙m) for one unit; not intended for tandem use
Audible Noise Rating
45 dBA at 1 m
Rotation Range
0 to 90° in 5-degree increments, mechanically limited to 93°
Rotation Time
30 seconds at 50% rated load, 25 to 50 seconds for 0 to 70 lb∙in (0 to 8 N∙m)
Electrical Connection
Screw terminals for 22 to 14 AWG; maximum of two 18, 20, or 22 AWG per terminal
Mechanical Connection
3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or 3/8 to 5/8 in. (10 to 16 mm) square
shaft
Enclosure
NEMA 2, IP42
Ambient Conditions
Operating: -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing
Storage: -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing
Dimensions (H x W x D)
7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm)
Shipping Weight
2.9 lb (1.3 kg)
Agency Compliance
UL Listed, File E27734, CCN XAPX
CSA Certified, File LR85083, Class 3221 02
CE Mark, EMC Directive 89/336/EEC
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
Johnson Controls
507 E. Michigan Street
P.O. Box 423
Published in U.S.A.