M9208-xxx-x Series Electric Spring Return Actuators (Continued)
Ambient
Conditions
Standard Operating -40 to 140°F (-40 to 60°C); 90% RH Maximum, Noncondensing
Storage -40 to 185ºF (-40 to 85ºC); 95% RH Maximum, Noncondensing
Dimensions 6.33 x 3.90 x 2.26 in. (160.7 x 99 x 57.5 mm)
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
Automatic Electrical Controls for Household and Similar Use; and
UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric Actuators. (Models: All)
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA:
July 2002, 3rd Ed., Automatic Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93
Temperature Indicating and Regulating Equipment (Models: All).
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC and Low Voltage Directive
2006/95/EC.
Australia and
New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant (Models: All)
Shipping Weight Models: -AGA: 3.43 lb (1.6 kg)
Models: -AGC: 3.8 lb (1.7 kg)
M9208-Bxx-3 Series On/Off Electric Spring Return Actuators (Part 1 of 2)
Power Requirements -BGx Models AC 24 V (AC 18 V to 30 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV)
(Europe), 6.1 VA Running, 1.2 VA Holding Position
DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe), 3.5 W Running, 0.5 W Holding
Position
Minimum Transformer Size: 7 VA per Actuator
-BAx Models AC 120 V (AC 102 V to 132 V) at 60 Hz: 0.05 A Running, 0.03 A Holding Position
-BDx Models AC 230 V (AC 198 V to 264 V) at 50/60 Hz: 0.04 A Running, 0.03 A Holding Position
Auxiliary Switch Rating -xxC Models Two SPDT, Double-Insulated Switches with Gold over Silver Contacts:
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Spring Return Direction Is Selectable with Mounting Position of Actuator:
Actuator Side A Is Away from Damper or Valve: CCW Spring Return
Actuator Side B Is Away from Damper or Valve: CW Spring Return
Rated Torque Power On
(Running)
70 lb·in. (8 N·m) All Operating Temperatures
Power Off
(Spring Returning)
70 lb·in. (8 N·m) at Standard Operating Temperatures
53 lb·in. (6 N·m) at Extended Operating Temperatures
Rotation Range Maximum Full Stroke: 95°
Adjustable Stop: 35 to 95°, Maximum Position
Rotation Time
for 90 Degrees of Travel
Power On
(Running)
55 to 71 Seconds for 0 to 70 lb·in. (8 N·m) Load, at All Operating Conditions
60 Seconds Nominal at Full Rated Load (0.25 rpm)
Power Off
(Spring Returning)
13 to 26 Seconds for 0 to 70 lb·in. (8 N·m) Load, at Room Temperature
21 Seconds Nominal at Full Rated Load
39 Seconds Maximum with 70 lb·in. (8 N·m) Load at -4°F (-20°C)
108 Seconds Maximum with 53 lb·in. (6 N·m) Load at -40°F (-40°C)
Life Cycles 60,000 Full-Stroke Cycles with 70 lb·in. (8 N·m) Load
Audible Noise Rating Power On
(Running)
<47 dBA at 70 lb·in. (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Power On
(Holding)
<20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
<52 dBA at 70 lb·in. (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical Connections Actuator
(All Models)
48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm²) Conductors and
.25 in. (6 mm) Ferrule Ends
Auxiliary Switches
(-xxC Models)
48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm²) Conductors and
.25 in. (6 mm) Ferrule Ends
Conduit Connections Integral Connectors for 3/8 in. (10 mm) Flexible Metal Conduit
M9208-AGx-x Series On/Off and Floating Point Control Electric Spring Return Actuator (Part 2 of 2)