Selection Guide

Non-Spring
Return Actuator
Product Range
Rotation
Time
90°
Power
Requirements
Power
Consumption
Input Signal
Position
Feedback
Auxiliary
Switches
Electrical
Connection
Power On - Running (seconds)
24 VAC +25%/-20%, Class 2, SELV
24 VAC +25%/-15%, Class 2, SELV
24 VAC +25%/-15%, VDC +/- 10%
VA Rating, Transformer Sizing
VA: Running (Holding)
Floating Point without Timeout
On/Off and Floating Point
Resistive 100 to 10,000 Ω
0(2) to 10 VDC
0(4) to 20 mA (w/500Ω Resistor)
Adjustable Start and Span:
Start: 0 to 10 VDC, Span 2 to 10 VDC
Resistive 135 Ω Potentiometer
Resistive 1,000 Ω Potentiometer
Resistive 10,000 Ω Potentiometer
0(2) to 10 VDC
2 SPDT, 3.0 A (1.5 A Inductive) @ 24 VAC
48 in. (1.2 m) 19 AWG Plenum Cable
Screw Terminals
¼” Spade Terminals
¼” Spade Terminals w/Pluggable Terminal. Block
½” conduit connectors
M9102 Series
18 in-lb (2) Nm
and
M9104 Series
35 in-lb (4) Nm
M9102-AGA-2S
30
2.1 2.1 (0)
M9102-AGA-3S
30
2.1 2.1 (0)
M9102-IGA-2S
30
2.6 2.6 (0.4)
M9102-IGA-3S
30
2.6 2.6 (0.4)
M9104-AGA-2S
60
2.1 2.1 (0)
M9104-AGA-3S
60
2.1 2.1 (0)
M9104-IGA-2S
60
3.0 3.0 (0.4)
M9104-IGA-3S
60
3.0 3.0 (0.4)
M9104-GGA-2S
60
3.6 3.6 (1.0)
M9104-GGA-3S
60
3.6 3.6 (1.0)
M9104-AGx-
2N0x Series
35 in-lb (6 Nm)
and
M9106-AGx-
2N0x Series
VAV Systems
53 in-lb (6 Nm)
M9104-AGA-2N
90
2.1 2.1 (0)
M9104-AGS-2N*
90
2.1 2.1 (0)
M9106-AGA-2N01
60
2.5 2.5 (0)
M9106-AGA-2N02
120
2.1 2.1 (0)
M9106-AGS-2N02*
* Includes DPT-2015
Differential Pressure
Transmitter and
CBL-2000-1 Wire
Harness
120
2.1 2.1 (0)
M9106 Series
53 in-lb (6 Nm)
M9106-AGA-2
60
2.5 2.5 (0)
M9106-AGC-2
60
2.5 2.5 (0)
M9106-AGF-2
60
2.5 2.5 (0)
M9106-IGA-2
60
2.8 2.8 (0.5)
M9106-IGC-2
60
2.8 2.8 (0.5)
M9106-GGA-2
60
3.2 3.2 (0.5)
M9106-GGC-2
60
3.2 3.2 (0.5)
M9109 Series
80 in-lb (9 Nm)
M9109-AGA-2
60
2.5 2.5 (0)
M9109-AGC-2
60
2.5 2.5 (0)
M9109-GGA-2
60
3.2 3.2 (0.5)
M9109-GGC-2
60
3.2 3.2 (0.5)
Factory Set for 60 seconds, User selectable for 90, 120, 330, and 660 seconds.