NS Series Network Sensors (Continued)
Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing; 85°F (29°C) Maximum Dew Point
Storage with LCD Display: -4 to 140°F (-20 to 60°C); 5 to 95% RH, Noncondensing
Storage without LCD Display: -40 to 158°F (-40 to 70°C); 5 to 95% RH, Noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
Note: Excludes the NS-ATV700x-0 and NS-BTV700x-0 models.
United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
other relevant provisions of the EMC Directive 2004/108/EC.
Australia and New
Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Accessory (Order Separately) NS-WALLPLATE-0: Adapts an 80 x 80 mm NS Series Network Zone Sensor to a Standard 80 x 120 mm Wallbox
Shipping Weight NS-Axx7xxx-0 Models: 0.20 lb (0.09 kg)
NS-Bxx7xxx-0 and NS-Mxx700x-0 Models: 0.25 lb (0.11 kg)
NS Series Network Zone Sensors — Motion Detection Only Models (No Temperature or Humidity Sensing)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
Current Consumption 13 mA Maximum (Non-transmitting)
Terminations Modular Jack or Screw Terminal Block
Sensor Addressing
(NS-MNN7003-0 Model)
DIP Switch Set from 200 to 203; Factory Set at 203
Wire Size Modular Jack Model: 24 AWG or 26 AWG (0.5 or 0.4 mm Diameter) Recommended;
Three Twisted Pair (Six Conductors)
Screw Terminal Block Model: 18 to 22 AWG (1.0 to 0.6 mm Diameter);
22 AWG (0.6 mm Diameter) Recommended
Communication Rate Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Mounting Surface-Mounted or Vertical Wallbox-Mounted: 120 x 80 mm
PIR Occupancy Sensor
Motion Detection
Minimum 94 Angular Degrees up to a Distance of 15 ft (4.6 m);
Based on a Clear Line of Sight
Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing; 85°F (29°C) Maximum Dew Point
Storage: -40 to 158°F (-40 to 70°C); 5 to 95% RH, Noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
other relevant provisions of the EMC Directive 2004/108/EC.
Australia and
New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight 0.25 lb (0.11 kg)
NS Series Network Zone Sensor — CO
2
Models (Part 1 of 2)
Supply Voltage Non-isolated: 20 to 30 VAC (18 to 30 VDC), Class 2 or Safety Extra-Low Voltage (SELV)
Isolated: 9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
Current Consumption Non-isolated: 22 mA Average at 24 VAC; 28 mA Average at 24 VDC
Isolated: 5 mA Maximum, Non-transmitting (From SA Bus)
Power Consumption Non-isolated: Less Than 0.7 W Average
Terminations Non-isolated Supply: Screw Terminal Block
SA Bus: Modular Jack or Screw Terminal Block
Sensor Addressing DIP Switch Set from 212 to 219; Factory Set at 212
Wire Size Modular Jack: 24 or 26 AWG (0.5 or 0.4 mm Diameter) Recommended; Three Twisted Pair (Six Conductors)
Screw Terminal Block: 18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter) Recommended
Communication Rate Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
CO
2
Measurement Range 0 to 2,000 ppm
NS Series Network Zone Sensors — Temperature Only Models and Temperature and Humidity Models (Part 2 of 2)