Product Overview

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc.
www.johnsoncontrols.com
6
NS Series Network Sensors (Continued)
CO
2
Sensing Accuracy Plus or Minus the Sum of 50 ppm and 3.0% of the CO
2
Reading at 77°F (25°C) and 978 hPa or an Altitude of
1,000 ft/300 m
Note: All accuracy specifications reflect the testing of the device using high-grade certified gases. This device is
intended for an altitude range of 0 ft/0 m to 2,000 ft/600 m above sea level without compensation.
Temperature Dependence of Output: -0.35% of the CO
2
Reading per 1.8F°/1C° Typical
Pressure Dependence of Output: +0.15% of the CO
2
Reading per 1 hPa Typical
CO
2
Sensing Resolution 1 ppm
CO
2
Sensing Response Time 1 Minute (0 to 90%)
CO
2
Sensing Warm-Up Time Less Than 1 Minute; Less Than 10 Minutes for Full Accuracy
CO
2
Sensing Long-Term Stability Less Than ±100 ppm Over 5 Years
Mounting Surface-Mounted or Vertical Wallbox-Mounted: 120 x 80 mm
Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing; 85°F (29°C) Maximum Dew Point;
700 to 1,200 hPa
Storage: -40 to 158°F (-40 to 70°C); 0 to 95% RH, Noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
United States UL Listed, File E107041 CCN PAZX, Under UL 916, Energy Management Equipment;
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
other relevant provisions of the EMC Directive 2004/108/EC.
Australia and New
Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Supply Voltage 0.35 lb (0.16 kg)
NS Series Network Zone Sensor — Flush-Mount Temperature Only Models
Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
Current Consumption 12 mA Maximum (Non-transmitting) per Flush-Mount Network Sensor
Terminations Screw Terminal Block
Note: Wire leads are field supplied and are not tinned.
Sensor Addressing DIP Switch Set from 200 to 203; Factory Set at 203
Wire Size 18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter) Recommended;
10 ft (304.8 cm) Wiring Lead Included with the Unit
Communication Rate Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Temperature Measurement Range 32.0°F/0.0°C to 104.0°F/40.0°C
Temperature Sensor Type Local 1k ohm Platinum Resistance Temperature Detector (RTD);
Class A per IEC 60751
Temperature Accuracy NS Series Network Zone Sensor: ±1.0F°/±0.6C°
Temperature Element Only: 0.35F° at 70°F (0.19C° at 21°C)
Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing; 85°F (29°C) Maximum Dew Point
Storage: -40 to 158°F (-40 to 70°C); 5 to 95% RH, Noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Australia and New
Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight 0.25 lb (0.11 kg)
NS Series Network Discharge Air Sensors (Part 1 of 2)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal
Current Consumption 12 mA Maximum (Non-transmitting) per Discharge Air Sensor
Terminations Four Color-Coded Wiring Leads, Stripped and Tinned;
Factory-Installed at the Discharge Air Sensor Screw Terminal Block
Sensor Addressing DIP Switch Set from 204 to 211; Factory Set at 204
NS Series Network Zone Sensor — CO
2
Models (Part 2 of 2)