NS Series Network Sensors (Continued)
Wire Size 18 to 22 AWG (1.0 to 0.6 mm Diameter);
22 AWG (0.6 mm Diameter) Recommended;
10 ft (305 cm) Wiring Lead Included with the Unit
Communication Rate Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Mounting Duct-Mounted: 4 or 8 in. (102 or 203 mm) Temperature Probe Length
Temperature Measurement Range 14°F/-10°C to 140°F/60°C
Temperature Sensor Type Local 1k ohm Platinum Resistance Temperature Detector (RTD);
Class A per IEC 60751
Temperature Accuracy NS Series Network Discharge Air Sensor: ±1.0F°/±0.6C°
Temperature Element Only: 0.35F° at 70°F (0.19C° at 21°C)
Ambient Conditions Operating: 14 to 140°F (-10 to 60°C); 10 to 90% RH, Noncondensing; 85°F (29°C) Maximum Dew Point
Storage: -40 to 158°F (-40 to 70°C); 5 to 95% RH, Noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
other relevant provisions of the EMC Directive 2004/108/EC.
Australia and New
Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight NS-DTN7043-0: 1.15 lb (0.52 kg)
NS-DTN7083-0: 1.17 lb (0.53 kg)
NS Series Network Discharge Air Sensors (Part 2 of 2)