Product Overview

P—
P470 Electronic Pressure Control with Display Product/Technical Bulletin
11
Table 2: Display Codes and How to Respond to Them
Flashing
Display
Code
What the Display Codes Indicates, and How to Respond to Them
EE
Indicates the control’s operating pressure range has been changed, both P6 jumpers are in the Installed
position, or a program failure has occurred. Ensure that the P6 jumpers are positioned for the correct pressure
range. (See Table 1.) Press the Menu button twice to reset the control for a new operating pressure range.
If ‘EE’ is still displayed, a program failure has occurred and the control must be replaced.
A x
A flashing ‘A x’ alternating with a flashing ‘XXX
psi
indicates the control is in an Anti-Short Cycle delay
sequence. The ‘x’ in ‘A x’ indicates the minutes of remaining Anti-Short Cycle delay. 0 minutes indicates the
control is in the final minute of the delay. ‘XXX
psi
’ indicates the sensed pressure value in this display.
ci1
Indicates that the primary cut-in setpoint may be changed by pressing the Menu button once to display the
current ‘ci1’ value (‘XXX
psi
’). Then press the Up or Down buttons to change the current ‘ci1’ value.
co1
Indicates that the primary cutout setpoint may be changed by pressing the Menu button once to display the
current ‘co1’ value (‘XXX
psi
’). Then press the Up or Down buttons to change the current ‘co1’ value.
ci2
Indicates that the secondary cut-in setpoint may be changed by pressing the Menu button once to display the
current ‘ci2’ value (‘XXX
psi
’). Then press the Up or Down buttons to change the current ‘ci2’ value.
co2
Indicates that the secondary cutout setpoint may be changed by pressing the Menu button once to display the
current ‘co2’ value (‘XXX
psi
’). Then press the Up or Down buttons to change the current ‘co2’ value.
ASd
Indicates that the Anti-short Cycle delay may be changed by pressing the Menu button once to display the
current Anti-short Cycle delay time in minutes. Then press the Up or Down buttons to change the current
Anti-short Cycle delay to any whole-minute value between 0 and 9 minutes.
XXX
psi
Indicates the current pressure setpoint value (in psi) for either ‘ci1’, ‘co1’, ‘ci2’, or ‘co2’, depending on the
previously displayed Display Code. Press the Up or Down buttons to change the setpoint value.
*
Err
Indicates that an invalid pressure setpoint has been entered, and the resulting setpoint differential is less than
the required minimum setpoint differential. Press the Up or Down buttons to create a setpoint differential that
is greater than or equal to the required minimum differential for the selected operating pressure range.
*The
Err
display code does not flash.
O
rdering Information
Table 3: Ordering Table for P470 Controls, P399 Transducers and Wiring Harnesses
Item Product Code Description
P470 (Low-Voltage)
Electronic Pressure
Control with Display
P470FB-1C
Low Voltage (<30 VAC) Electronic Pressure Control with Display
Supply Voltage: 24 VAC Class 2 Transformer
(See
Specifications
for complete Relay Electrical Ratings.)
P470 (Line-Voltage)
Electronic Pressure
Control with Display
P470EB-1C Line Voltage Electronic Pressure Control with Display
Supply Voltage: 120 or 208/240 VAC
(See
Specifications
for complete Relay Electrical Ratings.)
P399AAA-1C 0 to 100 psi Pressure Transducer with 1/8 in. NPT Male Fitting
P399AAC-1C 0 to 100 psi Pressure Transducer with 1/4 in. SAE (Schrader) Female Fitting
with integral valve depressor
P399BAA-1C 0 to 500 psi Pressure Transducer with 1/8 in. NPT Male Fitting
P399BAC-1C 0 to 500 psi Pressure Transducer with 1/4 in. SAE (Schrader) Female Fitting
with integral valve depressor
P399CAA-1C 0 to 750 psi Pressure Transducer with 1/8 in. NPT Male Fitting
P399 Electronic
Pressure Transducers
P399CAC-1C 0 to 750 psi Pressure Transducer with 1/4 in. SAE (Schrader) Female Fitting
with integral valve depressor
WHA-P399-200C 6 ft 6-1/2 in. (2m) 3-Wire Cable with Plug-in Connector for P399 Transducer
Wiring Harnesses for
P399 Transducers
WHA-P399-400C 13 ft 3 in. (4m) 3-Wire Cable with Plug-in Connector for P399 Transducer
Note: P470 controls do not include a transducer or wiring harness. Transducer and wiring harness must be
purchased separately. P399 transducer must be matched to the selected pressure range. See Table 1.