Product Overview

12 P—
P470 Electronic Pressure Control with Display Product/Technical Bulletin
S
pecifications
Product P470 Electronic Pressure Control with Display
Operating Pressure
Ranges
0 to 100 psi 0 to 500 psi 50 to 750 psi
Minimum Differential
Pressure
5 psi 20 psi 20 psi
Displayed Resolution 1 psi 3 psi 5 psi
Control Accuracy + 1.5 % of selected Operating Pressure Range plus transducer accuracy
Supply Voltage P470FB-1: 24 VAC, 50/60 Hz, Class 2
P470EB-1: 120 or 208/240 VAC, 50/60 Hz
Power Consumption 1.8 VA Maximum
Output Relay Contacts
Electrical Ratings
P470FB-1 (24 volt model): 100 VA, 30 VAC maximum, Class 2
P470EB-1 (120 or 208/240 volt model): 120V 208V 240V
Horsepower N.O. (N.C.) : 1 (1/4) hp 1 (1/3) hp 1 (1/2)
hp
Full Load Amperes N.O. (N.C.): 16 (5.8)A 9.2 (4.0)A 8.0 (4.9)A
Locked Rotor Amperes N.O. (N.C.): 96 (34.8)A 55.2 (24)A 48 (29.4)A
Non-inductive Amperes N.O. (N.C.): 15 (10)A 10 (10)A 10 (10)A
Pilot Duty: 125 VA (N.O.) @ 24 to 240 VAC
125 VA (N.C.) @ 120 to 240 VAC
50 VA (N.C.) @ 24 VAC
Transducer Type P399 Electronic Pressure Transducer (See Table 1 for model selection information.)
Ambient Temperature
at Control
Operating: -30 to 140°F (-34 to 60°C)
Shipping: -40 to 185°F (-40 to 85°C)
Ambient Humidity
at Operating Control
0 to 95% RH non-condensing;
Maximum Dew Point: 85°F (29°C)
Enclosure Case and Cover: NEMA 1 High-impact Thermoplastic
Agency Information UL: File SA516; CCN SDFY Canadian UL: File SA516; CCN SDFY7
FCC/DOC Part 15, Class A
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, contact Refrigeration Application Engineering at (800) 275-5676. Johnson Controls, Inc. shall not be liable for damages
resulting from misapplication or misuse of its products.
Controls Group FAN 125
507 E. Michigan Street Master Catalog
P.O. Box 423 Printed in U.S.A.