Specification Sheet

P499 Series Electronic Pressure Transducers Product/Technical Bulletin
10
® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
United States of America and/or other countries. All other trademarks used herein are the property
of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved.
www.penncontrols.com
Supply voltage 0.5 VDC to 4.5 VDC
ratiometric output
5.0 ±0.25 VDC, Safety Extra-Low Voltage (SELV) or Class 2
4 mA to 20 mA output 9 VDC to 30 VDC, SELV or Class 2
0 VDC to 10 VDC
output
12 VDC to 30 VDC, SELV or Class 2
Direct-mount pressure connections 1/8in. -27 NPT External Thread (Style 49),
1/4 in. SAE 45 Flare Internal Thread (7/16-20 UNF) with Depressor (Style 47)
Temperature and
humidity
Storage -40F to 257F (-40C to 125C)
Operating -40F to 185F (-40C to 85C)
Compensated range -4 toF 185F (-20C to 85C)
Humidity 0 to 100% RH
Linearity ±0.25% Full Span Best Fit Straight Line
Accuracy ±1% Full Span (maximum) over compensated temperature range
Materials Pressure port 17-4PH stainless steel construction
Packard
connector
40% glass-filled Polyetherimide (PEI)
Vibration 20G, 20 to 200 Hz
Shock 200G / 11 ms
Compliance United States UL Listed, File E29374, CCN NKPZ
UL Recognized for Use in Class I, Division 2 Hazardous Locations,
File E322274
Canada UL Listed, File E29374, CCN NKPZ7
UL Recognized for Use in Class I, Division 2 Hazardous Locations,
File E322274
Europe CE Mark – Johnson Controls declares that this product is in compliance with
the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC
Australia/
New Zealand
C-Tick Mark, Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/PENN Refrigeration Application Engineering at 1-800-275-5676. Johnson Controls shall not be liable
for damages resulting from misapplication or misuse of its products.
P499 Series Electronic Pressure Transducers (Part 2 of 2 )