RLD-H10G Refrigerant Leak Detector
Code No. LIT-1927315
Issued November 13, 2015
Description
The RLD-H10G is a professional grade leak
detector for use by refrigeration and air
conditioning technicians. This detector senses
all CFC, HCFC, and HFC refrigerants and
blends, such as R12, R502, R22, R404a,
R507, R134a and R410A, among others. The
RLD-H10G plugs into a 120 VAC outlet.
Features
• positive ion emission heated diode sensor
provides the most sensitivity available
today, while still detecting all halogenated
refrigerant gases
• halogen selective sensing eliminates many
sources of possible false alarms due to
background contamination
• high quality air pump supplies constant air
flow to sensor so it responds quickly to
leaks; also helps sensor recover quickly
after exposure to refrigerant so leak can be
verified
• visual and audible signal facilitates sensing
in noisy equipment rooms with 360°
visibility and piercing tone; frequency of
noise/light indicates magnitude of leak
• exceeds SAE J1627 moving probe
specification; minimizes service time
because the leak is found the first time, is
verifiable, and the fix can be confirmed
• external calibration source indicates when
the sensor is working properly and serves
as a reference point to judge leak size
Selection Chart
For repair parts, contact your local
Johnson Controls/PENN representative.
Accessories
Code
Number
Description
RLD-H10G-1 Refrigerant Leak Detector control
unit with a manual balancing
circuit, a probe with a 4.5 ft cable,
and a 6 ft power cord
Code
Number
Description
RLD-H10-100 14 inch flexible probe extension
RLD-H10-600R Tune-up kit includes: sensor,
100 filters, 3 airflow indicator
balls, 3 probe tips and leak vial
RLD-H10-601R Replacement sensor
RLD-H10-602R Maintenance kit includes:
100 replacement filters,
3 airflow indicator balls, and
3 probe tips
RLD-H10-603R Replacement leak vial
RLD-H10-606R Replacement clear plastic probe
tip
RLD-H10-607R Replacement probe assembly
Technical Specifications
RLD-H10G Refrigerant Leak Detector
Power Requirements 120 VAC at 60 Hz
Sensing Element Type Positive Ion Emission Heated Diode
Approximate
Sensitivity
Switch Position Alarm Sensitivity (moving probe)
Small >0.05 oz per year CFC or HCFC; >0.5 oz per year HFC
Medium >0.5 oz per year CFC or HCFC; >1.0 oz per year HFC
Large >3.0 oz per year CFC or HCFC; >5.0 oz per year HFC
Leak Alarm Audible alarm, visible neon lamp
Response Time Approximately 1 second
Warm-up Time Approximately 2 minutes
Accuracy Meets SAE J1627 test requirements
Probe Length Approximately 4.5 ft (1.4 m)
Ambient Operating
Conditions
32 to 113° F (0 to 45° C); 5 to 90% RH, non-condensing
Ambient Storage
Conditions
14 to 140° F (-10 to 60° C); 5 to 90% RH, non-condensing
Case Vinyl
Dimensions
(H x W x D)
2.8 x 8.8 x 5.0 in. (71 x 224 x 127 mm)
Shipping Weight 3.2 lbs (1.4 kg)
RLD-H10G