Submaster High Volume Output Thermostat
Description
The T-4003 Submaster Thermostat is a high
volume proportional thermostat. The T-4003
can be reset from a remote location, or in
accordance with a referenced temperature
variation.
Refer to T-4000 Series Pneumatic Room
Thermostat Product Bulletin (LIT-7171060P)
for important product information.
Selection Charts
Note: For additional accessories, refer to T-4000 Series Accessories.
T-4003 Submaster Thermostat
1
1. Order cover and mounting bracket separately.
Code Number Description
T-4003-201 Direct Acting, Horizontal Mounting
T-4003-203 Reverse Acting, Horizontal Mounting
Commonly Used Accessories for T-4003
Code
Number
Description
T-4002-124 Room instrument mounting bracket for
surface-mounting thermostats and
covers; includes drywall clips, spacers,
and mounting templates
T-4512-100 Terminal Connector, with three straight
fittings for plug-in connection to
5/32 in. O.D. polyethylene tubing
T-4002-5003 Restricted adjustment pin (100/kit)
restricts adjustment of set point dial
T-4000-2138 Beige Plastic Cover, Horizontal or
Vertical (no thermometer, no set point
windows)
T-4000-2139 Beige Plastic Cover, Horizontal (no
thermometer, no set point windows)
T-4000-3139 White Plastic Cover, Horizontal (no
thermometer, no set point windows)
T-4000-2140 Beige Plastic Cover, Horizontal,
thermometer (no set point windows)
T-4000-3140 White Plastic Cover, Horizontal,
thermometer (no set point windows)
T-4000-2141 Beige Plastic Cover, Horizontal,
1 set point window (no thermometer)
T-4000-3141 White Plastic Cover, Horizontal,
1 set point window (no thermometer)
T-4000-2142 Beige Plastic Cover, Horizontal,
1 set point window with thermometer
T-4000-3142 White Plastic Cover, Horizontal,
1 set point window with thermometer
Technical Specifications
T-4003 Submaster High Volume Output Thermostat
Sensitivity Fixed at approximately 2.5 psig/°F (32 kPa/°C)
Remote Reset Adjustable from 0.15 psig to 2.5 °F/PSI (1.8 to 30°C/kPa)
Flow Capacity 400 SCIM (107 mL/s)
Air Consumption 20 SCIM (5 mL/s)
Supply Pressure 13 to 25 psig (91 to 175 kPa), Nominal 20 psig (140 kPa)
Master Pressure Variable Input 0 to 20 psig (0 to 140 kPa)
Dial Range 55 to 85°F
Air Connections Three (Supply, Output, Remote Reset Input)
Code No. LIT-1921665
Issued January 15, 2008
T-4003 Submaster Thermostat
Features
available in Direct Acting (DIR) and
Reverse Acting (REV) models
includes Fahrenheit dial
available in horizontal model only
Repair Information
If the T-4003 Submaster Thermostat fails to
operate within its specifications, replace the
unit. For a replacement thermostat, contact
the nearest Johnson Controls®
representative.