Product Overview
Table Of Contents
TE-6300 Series Temperature Sensors Product Bulletin2
Product Overview
All TE-6300 Series sensors are two-wire, passive,
resistance-output devices.
TE-63xxA Models
The TE-63xxA (adjustable length) models:
• provide a thermoplastic mounting flange and gland
nut to adjust the length of the probe
• include two hex-head self-drilling screws for
mounting
• come equipped with a 10 ft (3 m) plenum-rated
cable with a 2-position plug terminal block for
1/4 in. (6.35 mm) male tab terminals on
0.197 in. (5 mm) centers, for direct connection to
Johnson Controls VMA controller products
TE-63xxF Models
The TE-63xxF (flush mount) models:
• provide a low profile when installed in an electrical
box
• feature thermally isolated sensor from the wall with
a foam pad
• offer a rugged stainless steel cover
• provide 22 AWG lead wires with low voltage
installation
TE-63xxM Models
The TE-63xxM (metal enclosure) models:
• come with a corrosion-protected steel enclosure
with a 0.88 in. (22 mm) hole for a 1/2 in. (12.7 mm)
conduit fitting
• include two hex-head self-drilling screws for
mounting the duct and duct averaging models
• offer (for well models only) either a direct-mount or
1/2-14 NPT threaded well sensor holder for
mounting in TE-6300W Series thermowells (order
the thermowell separately)
• provide optional well sensor holders (order
separately) to mount duct models in thermowells
• meet UL 1995 plenum use requirements
• offer an optional accessory kit (order separately) to
replace plastic hole plug and wiring bushing to
meet International Mechanical Code (IMC)
requirements
TE-63xxP Models
The TE-63xxP (plastic enclosure) models:
• provide a thermoplastic conduit box with
1/2-14 NPT female thread for connecting to conduit
• provide aluminum mounting plate and 1/2-14 NPT
threaded hub mounting options for the duct and
duct-averaging models
• use the 1/2-14 NPT female thread to mount the
Outdoor Air models directly to ridged conduit
• provide sensor holders included to mount duct
models in thermowells (order thermowell
separately)
• offer an optional accessory metal cover kit (order
separately) to replace the plastic cover to meet
UL 1995 plenum use requirements
• include a replaceable sensing probe on
duct-probe, outdoor-air, and well-insertion models
TE-63x4P Wall Mount Models
The TE-63x4P (plastic enclosure) models:
• come with a white thermoplastic ventilated cover
with a brushed aluminum face plate and a steel
mounting plate for surface mounting
• include faceplates for both horizontal and vertical
mounting
• offer an accessory mounting kit for mounting to a
standard electrical box
• offer optional covers
TE-63xS Models
The TE-63xS (Strap-Mount) models:
• provide a 1/4 in. (6.35 mm) diameter stainless steel
probe without an enclosure
• include three cable ties for mounting to pipe up to
2-5/8 in. (67 mm) diameter
• come equipped with a 10 ft (3 m) plenum-rated
cable
• meet UL 1995 plenum use requirements
IMPORTANT: The TE-6300 Series Temperature
Sensors are intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the sensor could
lead to personal injury or property damage to the
controlled equipment or other property, additional
precautions must be designed into the control
system. Incorporate and maintain other devices,
such as supervisory or alarm systems or safety or
limit controls, intended to warn of or protect against
failure or malfunction of the sensor.