User Guide
Table Of Contents
TE-6300P Series Temperature Sensors Installation Instructions4
Mounting the Well Insertion Sensor
See Figure 8 and mount the sensor as follows:
Note: Add thermal grease (F-1000-182, or equivalent)
before inserting the probe if the well does not include
thermal grease. For proper sensor function, mount the
well so that any condensation that forms drains out of
the probe.
1. Loosen the sensor holder setscrew and remove the
probe.
2. If the thermal well is:
• Threadless (TE-63xAP-1), see Figure 9 and
loosen the two well set screws (the
TE-6300W-103 contains thermal grease).
Insert the sensor holder, then tighten the well
set screws.
• Threaded (TE-63x2P-1), see Figure 10 and
screw the sensor holder into the thermal well.
3. Insert the sensor probe through the sensor holder
and into the thermal well until it just touches the
base.
4. Back the probe out approximately 1/8 in. (3 mm)
and tighten the sensor holder set screw.
5. Pull the sensor wires into the conduit box and snap
the conduit box onto the sensor holder.
6. Install the retainer into the sensor holder.
7. Wire the sensor to the controller using the wire nuts
provided.
8. Reposition the cover and tighten the retention
screws.
Figure 8: Installing the Well Insertion Sensor
F
I
G
:
i
n
s
_
w
_
s
n
s
To Controller
Retainer
Sensor Probe
Sensor Holder
Thermal Well
Figure 9: Installing the Threadless Sensor Holder
F
I
G
:
t
h
r
d
l
s
Thermal Well
TE-6300-103
Threadless Mounting
Set Screws
Sensor Holder
Set Screw
Figure 10: Installing the Threaded Sensor Holder
F
I
G
:
t
h
r
d
Threaded Mounting
TE-6300W-110
Thermal Well
Sensor Holder
Set Screw
1/2-14 NPT
Threads