Product Overview
Table Of Contents
TE-6300 Series Temperature Sensors Product Bulletin6
For specific TE-6300 Series Temperature Sensor
applications, see Table 3.
Table 3: TE-6300 Series Temperature Sensor Applications (Part 1 of 2)
Application
Nominal
Probe
Length,
in. (mm)
Sensor Type Application Notes
Duct Probe 4 (102)
8 (203)
18 (457)
1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
2.2k ohm Thermistor
10k ohm Thermistor
Type II
• Ideal in freezer lockers or for mounting outside of the sensed area.
• Available with plastic enclosure, metal enclosure, flange mount, or with
mounting bracket for adjustable length.
• Use TE-63xxM or TE-63xxV models for plenum applications.
• Use TE-6300-613 accessory kit with TE-63xxM models to meet
IMC requirements.
• Use TE-6001-13 metal cover kit with TE-63xxP models to meet UL 1995
plenum requirements.
• Order an optional TE-63xxP model accessory: 12 in. (300 mm) probe.
Duct
Averaging
Element
8 ft
(2.4 m)
10 ft (3 m)
17 ft
(5.2 m)
20 ft
(6.1 m)
1k ohm Nickel Wire
100 ohm Platinum
Equivalent Wire
1k ohm Platinum
Equivalent Wire
• Use to sense duct temperature where stratification can occur, such as
mixed air ducts.
• Duct averaging models come in three styles: plastic enclosure, metal
enclosure, or flange mount.
• Use about 1 ft (0.3 m) of sensor per sq ft (0.09 m
2
) of duct cross section.
• Use a series-parallel sensor network to cover larger ducts.
• Use a TE-6001-8 element holder (recommended) when installing an
averaging sensor in a duct.
• Use TE-63xxM or TE-63xxV models for plenum applications.
• Use TE-6300-613 kit with TE-63xxM models to meet IMC requirements.
• Use the TE-6001-13 metal cover kit with TE-63xxP models to meet
UL 1995 plenum requirements.
Outdoor Air 3 (76)
1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
2.2k ohm Thermistor
10k ohm Thermistor,
Type II
• Use to sense outside ambient temperature to determine efficient heating
and cooling strategies.
• Mount the sensor out of direct sunlight and away from exhaust vents or
equipment that can cause inaccurate temperature sensing.
Strap-
Mount
3 (76) 1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
10k ohm Thermistor,
Type II
• Clamp the probe directly to a pipe or the device to be sensed.
• Mount the probe away from fans or radiant heat that can affect
measurement of the sensed device.
• Use for plenum applications.
• Order an accessory mounting kit or use readily available hardware for
pipe up to 11 in. (280 mm) diameter.
Wall Mount N/A 1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
2.2k ohm Thermistor
• Use to sense room or space temperature.
• Order an accessory cover with a thermometer or to match the style of
existing installations.
• Mount the sensor on an inside wall, out of direct sunlight and away from
radiant heat.
Wall Plate
Flush
Mount
N/A Flush Mount 1k ohm
Nickel Sensor
Flush Mount 1k ohm
Platinum Sensor
Flush Mount 10k ohm
NTC Sensor
• Flush mount 10k ohm NTC sensor: do not install the flush mount sensor
in temperatures beyond 0–40°C
• Use copper conductors only. Refer to installation diagrams for
recommended wiring lengths.