Product Overview

TE-6300 Series Temperature Sensors Product Bulletin6
For specific TE-6300 Series Temperature Sensor
applications, see Table 3.
Table 3: TE-6300 Series Temperature Sensor Applications (Part 1 of 2)
Application
Nominal
Probe
Length,
in. (mm)
Sensor Type Application Notes
Duct Probe 4 (102)
8 (203)
18 (457)
1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
2.2k ohm Thermistor
10k ohm Thermistor
Type II
Ideal in freezer lockers or for mounting outside of the sensed area.
• Available with plastic enclosure, metal enclosure, flange mount, or with
mounting bracket for adjustable length.
Use TE-63xxM or TE-63xxV models for plenum applications.
Use TE-6300-613 accessory kit with TE-63xxM models to meet
IMC requirements.
Use TE-6001-13 metal cover kit with TE-63xxP models to meet UL 1995
plenum requirements.
Order an optional TE-63xxP model accessory: 12 in. (300 mm) probe.
Duct
Averaging
Element
8 ft
(2.4 m)
10 ft (3 m)
17 ft
(5.2 m)
20 ft
(6.1 m)
1k ohm Nickel Wire
100 ohm Platinum
Equivalent Wire
1k ohm Platinum
Equivalent Wire
Use to sense duct temperature where stratification can occur, such as
mixed air ducts.
Duct averaging models come in three styles: plastic enclosure, metal
enclosure, or flange mount.
Use about 1 ft (0.3 m) of sensor per sq ft (0.09 m
2
) of duct cross section.
Use a series-parallel sensor network to cover larger ducts.
Use a TE-6001-8 element holder (recommended) when installing an
averaging sensor in a duct.
Use TE-63xxM or TE-63xxV models for plenum applications.
Use TE-6300-613 kit with TE-63xxM models to meet IMC requirements.
Use the TE-6001-13 metal cover kit with TE-63xxP models to meet
UL 1995 plenum requirements.
Outdoor Air 3 (76)
1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
2.2k ohm Thermistor
10k ohm Thermistor,
Type II
Use to sense outside ambient temperature to determine efficient heating
and cooling strategies.
Mount the sensor out of direct sunlight and away from exhaust vents or
equipment that can cause inaccurate temperature sensing.
Strap-
Mount
3 (76) 1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
10k ohm Thermistor,
Type II
Clamp the probe directly to a pipe or the device to be sensed.
Mount the probe away from fans or radiant heat that can affect
measurement of the sensed device.
Use for plenum applications.
Order an accessory mounting kit or use readily available hardware for
pipe up to 11 in. (280 mm) diameter.
Wall Mount N/A 1k ohm Thin-Film
Nickel
1k ohm Thin-Film
Platinum
2.2k ohm Thermistor
Use to sense room or space temperature.
Order an accessory cover with a thermometer or to match the style of
existing installations.
Mount the sensor on an inside wall, out of direct sunlight and away from
radiant heat.
Wall Plate
Flush
Mount
N/A Flush Mount 1k ohm
Nickel Sensor
Flush Mount 1k ohm
Platinum Sensor
Flush Mount 10k ohm
NTC Sensor
Flush mount 10k ohm NTC sensor: do not install the flush mount sensor
in temperatures beyond 0–40°C
Use copper conductors only. Refer to installation diagrams for
recommended wiring lengths.