Product Overview
Table Of Contents
TE-63xS Series Strap-Mount Temperature Sensors Installation Instructions 1
Applications
Installation
Dimensions
Mounting
Location Considerations
Consider the following mounting location guidelines:
• Avoid areas subject to excessive vibration,
electrical noise, direct sunlight, or the effects of
radiant heat.
• Keep electrical wiring as short as possible to
minimize temperature error.
Mounting the Sensor
See Figure 2 and mount the temperature sensor as
follows:
1. Mount the probe to the pipe using cable ties (three
included) or adjustable pipe clamps. Use thermal
conductive compound, F-1000-182 (order
separately), or equivalent, between the sensor and
pipe for best performance.
Note: Use Accessory Kit TE-6300-615 for pipe sizes
larger than 2 in. (51 mm) and up to 10 in. (250 mm)
and -40 to 220°F (-40 to 104°C) temperature range.
2. Wire the sensor to the controller.
Wiring
For 1k ohm nickel temperature sensors, wire
resistance can cause approximately 1F° (0.56C°) of
error for every 250 ft (76 m) run of 18 AWG (1.0 mm
diameter) wire, or every 100 ft (31 m) run of 22 AWG
(0.6 mm diameter) wire. To minimize error due to field
wiring, limit total resistance of all nickel temperature
sensor wiring to 3 ohms.
IMPORTANT: The TE-63xS Series Strap-Mount
Temperature Sensors are intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
sensor could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the sensor.
IMPORTANT: Do not install the TE-63xS Series
Strap-Mount Temperature Sensor probe in ambient
temperatures beyond the specified -50 to 220°F
(-46 to 104°C) temperature range. Installing the
temperature sensor in ambient temperatures
beyond this range may damage the unit and void the
warranty.
Figure 1: Sensor Dimensions, in. (mm)
F
I
G
:
s
n
s
_
d
i
m
3.0 (76)
IMPORTANT: If using adjustable metal pipe
clamps, do not overtighten the clamps.
Overtightening the clamps may damage the sensor
or cable.
Figure 2: Installing the Strap-Mount Sensor
F
I
G
:
s
n
s
_
i
n
s
t
To Controller
TE-63xS Series Strap-Mount Temperature Sensors
Installation Instructions
TE-631S-1, TE-635S-1
TE-636S-1
Part No. 24-4034-239, Rev. B
Issued April 6, 2010
Supersedes December 5, 2007