Install Instructions
Table Of Contents
- Applications
- North American Emissions Compliance
- United States
- Canada
- Installation
- Parts Included
- Location Considerations
- Installing the Thermostat Controller
- Wiring
- Setup and Adjustments
- Overview
- Customizing the Home Screen
- Touchscreen Icons
- User Lockout
- Using the USB Port
- Loading the Firmware
- Backing Up the Settings
- Restoring the Settings
- Choosing the Communication Mode (TEC3620-00-000, TEC3621-00-000, TEC3622-00-000, and TEC3623-00-000 Models)
- Configuring the Thermostat Controller
- Installer Configuration Menu
- Screen Reset
- Selecting the Unit Type
- By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or Pressure-Dependent VAV mode:
- Configuring the Supply Fan - Fan Coil Only
- Setting the Control Mode
- Setting the Fan Mode - Fan Coil Only
- Configuring the Zone Space or Equipment Size
- Changeover
- Dehumidification Control - Fan Coil Only
- Temperature Setpoints
- Configuring Occupancy
- Selecting Schedule Source
- Scheduling
- Setting the Local Schedule
- Overriding the Occupancy Mode
- Enabling Optimal Start
- Enabling the Motion Sensor (TEC3x21-00-000, TEC3x23-00-000 Models)
- PID/PRAC+ Automatic Control Tuning
- Configurable Binary Inputs
- Aux Control
- Commissioning Mode
- Sensor Priority
- Available Fault Diagnostics
- Menus and Submenus
- Troubleshooting
- Repair Information
- TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 2)
TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
29
Note: For more details on PID/PRAC+ Automatic Control Tuning, refer to the Controller Tool Help (LIT-12011147).
Configurable Binary Inputs
The thermostat controller supports up to two configurable binary inputs (BIs) that can be used to add additional
features to the system. Configurable Binary Inputs are accessed through Settings > Control Setup > Inputs. Both
BIs can be configured to support the following options:
• Disabled—Sets the binary input to an unused state. When disabled, you can use the binary input for
monitoring-only without affecting the thermostat functionality.
• Open Window—Sensor to shut down control if a window is opened. The controller disables control 60 seconds
after detecting an opened window.
• Open Door—Works in conjunction with the Motion NO/Motion NC sensor to control occupancy
• Fan Lock—Air Proof switch input to shut down control if no airflow is detected within 10 seconds of turning the
fan on. Fan Lock must be manually reset from the Faults menu.
• Service—Input from the equipment to display a service warning on the thermostat
• Dirty Filter—Input from the equipment to display a dirty filter fault on the thermostat
• Motion NC—External motion sensor with a closed contact output when no motion is detected
• Motion NO—External motion sensor with an open contact output when no motion is detected
• Temp Occ—Trigger to place controller into Temporary Occupancy mode
• Occupancy—Direct override of Occupied and Unoccupied
• Supply Fan Status—Input from the equipment to display a Supply Fan Fault. When Fan Alarm Action is set to
Shutdown and the Supply Fan Fault is active, the TEC3000 disables the fan, heating, and cooling. When the
Fan Alarm Action is set to Enable and the Supply Fan Fault is active, the TEC3000 allows the fan, heating, and
cooling to operate during the Supply Fan Fault.
Setting both BIs to the same function is supported for all except Occupancy, Fan Lock, Open Door, and Open
Window. If both BIs are set the same for those four, BI2 is ignored and only BI1 is used.
The Open Door option works in conjunction with a motion sensor, either built into the TEC or connected to another
BI configured for Motion NO/NC mode. When the door is open, motion detected by the sensor is ignored. Note that
opening the door does not stop an Occupied period started by the motion sensor prior to opening the door.
The polarity of the inputs are provided in Table 9.
Deadband Override There is no deadband in use with proportional devices. This operates in the same way
as Automatic PID tuning.
Manual PID Tuning Manual tuning of Heating and Cooling PIDs. The manual tuning parameters are listed
under Control Setup > Tuning in Table 10.
Table 9: Input Polarities
BI Configuration Contact Open Contact Closed
Occupancy Unoccupied Occupied
Temp Occ No Trigger Active
Temporary Occupancy Trigger
1
Motion NO No Motion Detected, Standby
Motion Detected, Occupied
1
Motion NC
Motion Detected, Occupied
1
No Motion Detected, Standby
Dirty Filter Dirty Filter Alarm Inactive
Dirty Filter Alarm
1
Service Service Alarm Inactive
Service Alarm
1
Table 8: TEC3000 Tuning Types
Tuning Type Description