Install Instructions
Table Of Contents
- Applications
- North American Emissions Compliance
- United States
- Canada
- Installation
- Parts Included
- Location Considerations
- Installing the Thermostat Controller
- Wiring
- Setup and Adjustments
- Overview
- Customizing the Home Screen
- Touchscreen Icons
- User Lockout
- Using the USB Port
- Loading the Firmware
- Backing Up the Settings
- Restoring the Settings
- Choosing the Communication Mode (TEC3620-00-000, TEC3621-00-000, TEC3622-00-000, and TEC3623-00-000 Models)
- Configuring the Thermostat Controller
- Installer Configuration Menu
- Screen Reset
- Selecting the Unit Type
- By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or Pressure-Dependent VAV mode:
- Configuring the Supply Fan - Fan Coil Only
- Setting the Control Mode
- Setting the Fan Mode - Fan Coil Only
- Configuring the Zone Space or Equipment Size
- Changeover
- Dehumidification Control - Fan Coil Only
- Temperature Setpoints
- Configuring Occupancy
- Selecting Schedule Source
- Scheduling
- Setting the Local Schedule
- Overriding the Occupancy Mode
- Enabling Optimal Start
- Enabling the Motion Sensor (TEC3x21-00-000, TEC3x23-00-000 Models)
- PID/PRAC+ Automatic Control Tuning
- Configurable Binary Inputs
- Aux Control
- Commissioning Mode
- Sensor Priority
- Available Fault Diagnostics
- Menus and Submenus
- Troubleshooting
- Repair Information
- TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 2)
TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
32
Menus and Submenus
In the following table, the * indicates that the menus depend on your configuration.
Table 10: Menus and Submenus (Part 1 of 8)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1
Setpoints Occ Cooling Setpoint 72°F (22°C) 55 to 85°F (13 to 30°C)
Occ Heating Setpoint 68°F (20°C) 55 to 85°F (13 to 30°C)
Unocc Cooling Setpoint 80ºF (27°C) 55 to 85°F (13 to 30°C)
Unocc Heating Setpoint 60°F (15°C) 55 to 85°F (13 to 30°C)
Stby Cooling Setpoint 74°F (23°C) 55 to 85°F (13 to 30°C)
Stby Heating Setpoint 66°F (19°C) 55 to 85°F (13 to 30°C)
Dehumidification* 50% RH 0 to 100% RH
*Dehumidification Enable = True
Occ Setpoint Select Setpoint Offset Min and Max Setpoint or Setpoint Offset
Heat Cool Setpoint Mode Individual
Setpoints
Common Setpoint or Individual Setpoint
Max Heating Setpoint* 68°F (20°C) The range (in degrees) from the Min
Heating Setpoint temperature to the Min
Cooling Setpoint temperature minus 1°F
(0.55°C). (The cooling temperature
always needs to be 1°F [0.55°C]above
the heating temperature.)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select == Min
and Max Setpoint.
Min Heating Setpoint* 60°F (15°C) 45°F (7.22°C) to Max Heating Setpoint
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select == Min
and Max Setpoint.
Max Cooling Setpoint* 80ºF (27°C) Min Cooling Setpoint to 100°F (37.77°C)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select == Min
and Max Setpoint.
Min Cooling Setpoint* 72°F (22°C) The range (in degrees) from the Max
Heating Setpoint temperature plus
1°F (0.55°C) to the Max Cooling Setpoint
temperature.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select == Min
and Max Setpoint.
Max Setpoint* 80ºF (27°C) Min Setpoint to 100°F (37.77°C)
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
Min Setpoint* 60°F (15°C) 45°F (7.22°C) to Max Setpoint
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.