Install Instructions
Table Of Contents
- Applications
- North American Emissions Compliance
- United States
- Canada
- Installation
- Parts Included
- Location Considerations
- Installing the Thermostat Controller
- Wiring
- Setup and Adjustments
- Overview
- Customizing the Home Screen
- Touchscreen Icons
- User Lockout
- Using the USB Port
- Loading the Firmware
- Backing Up the Settings
- Restoring the Settings
- Choosing the Communication Mode (TEC3620-00-000, TEC3621-00-000, TEC3622-00-000, and TEC3623-00-000 Models)
- Configuring the Thermostat Controller
- Installer Configuration Menu
- Screen Reset
- Selecting the Unit Type
- By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or Pressure-Dependent VAV mode:
- Configuring the Supply Fan - Fan Coil Only
- Setting the Control Mode
- Setting the Fan Mode - Fan Coil Only
- Configuring the Zone Space or Equipment Size
- Changeover
- Dehumidification Control - Fan Coil Only
- Temperature Setpoints
- Configuring Occupancy
- Selecting Schedule Source
- Scheduling
- Setting the Local Schedule
- Overriding the Occupancy Mode
- Enabling Optimal Start
- Enabling the Motion Sensor (TEC3x21-00-000, TEC3x23-00-000 Models)
- PID/PRAC+ Automatic Control Tuning
- Configurable Binary Inputs
- Aux Control
- Commissioning Mode
- Sensor Priority
- Available Fault Diagnostics
- Menus and Submenus
- Troubleshooting
- Repair Information
- TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 2)
TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
33
Schedule Schedule Options
Set Schedule
— See Scheduling
Optimal Start Enable No Yes or No
Temp Occ Duration 120 minutes 0 to 300 minutes
Motion Sensor Timeout 15 minutes 15 to 240 minutes
Manual Occupancy Mode No Override No Override, Occupied, Unoccupied
Schedule Source Local Local or BAS
Display Settings Passcode Enable No Yes or No
Passcode* NA 0000 to 9999
*Passcode Enable = Yes
Brightness Setting 8 0 to 10 (most dim to brightest)
Enable Backlight Timeout Yes Yes or No
Units IP IP or SI
Time N/A
—
Time Zone Central All World Time Zones
Set Time Format 24 hour 24 hour or 12 hour
Date N/A
—
Set Date Format YYYY-MM-DD YYYY-MM-DD, or Day, Month DD, YYYY,
or MM-DD-YYYY
Language English English, French, Spanish
Show Fan Icon Yes Yes or No
Show Temp Yes Yes or No
Show Humidity Yes Yes or No
Show Off Icon Yes Yes or No
Show Hold Icon Yes Yes or No
Show Setpoint Yes Yes or No
Show Alarms Yes Yes or No
Show Occ Status Yes Yes or No
Show Unit Status Yes Yes or No
Show Date/Time Yes Yes or No
Control Setup General
Control Mode Auto Auto, Cooling, or Heating
Unit Enable Enable Enable or Shutdown
Fan Mode* Smart On, Auto, and Smart for single- and
variable-speed fans. Low, Medium, High,
Auto, and Smart for multi-speed units.
* Fan Coil units only
Max Setpoint Offset 3 degrees 0 to 20 degrees (°F or °C based on Units
setting under Display Settings menu)
Fan On Delay* 30 seconds 0 to 120 seconds
* Fan coil units only
Table 10: Menus and Submenus (Part 2 of 8)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1