Install Instructions
Table Of Contents
- Applications
- North American Emissions Compliance
- United States
- Canada
- Installation
- Parts Included
- Location Considerations
- Installing the Thermostat Controller
- Wiring
- Setup and Adjustments
- Overview
- Customizing the Home Screen
- Touchscreen Icons
- User Lockout
- Using the USB Port
- Loading the Firmware
- Backing Up the Settings
- Restoring the Settings
- Choosing the Communication Mode (TEC3620-00-000, TEC3621-00-000, TEC3622-00-000, and TEC3623-00-000 Models)
- Configuring the Thermostat Controller
- Installer Configuration Menu
- Screen Reset
- Selecting the Unit Type
- By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or Pressure-Dependent VAV mode:
- Configuring the Supply Fan - Fan Coil Only
- Setting the Control Mode
- Setting the Fan Mode - Fan Coil Only
- Configuring the Zone Space or Equipment Size
- Changeover
- Dehumidification Control - Fan Coil Only
- Temperature Setpoints
- Configuring Occupancy
- Selecting Schedule Source
- Scheduling
- Setting the Local Schedule
- Overriding the Occupancy Mode
- Enabling Optimal Start
- Enabling the Motion Sensor (TEC3x21-00-000, TEC3x23-00-000 Models)
- PID/PRAC+ Automatic Control Tuning
- Configurable Binary Inputs
- Aux Control
- Commissioning Mode
- Sensor Priority
- Available Fault Diagnostics
- Menus and Submenus
- Troubleshooting
- Repair Information
- TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 2)
TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
34
Control Setup
(Cont)
Fan Off Delay* 30 seconds 0 to 120 seconds
* Fan coil units only
Frost Protection Yes Yes or No
Dehumidification Enable* No Yes or No
* Fan coil units with humidity sensor
Aux Mode Not Used Not Used, Occupied NO, Occupied NC,
Occupied Fan NO, Occupied Fan NC, On,
Off
Load Shed Rate Limit 0.066°F 0 to 1°F (0 to 0.5°C)
Load Shed Adjust 4°F 0 to 8°F (0 to 4°C)
Fan Alarm Delay 0 seconds 0 to 300 seconds
Fan Alarm Action* Enable Enable or Shutdown
* Fan Alarm Delay > 0
Fan Alarm Reset* No Yes or No
* When Fan Alarm Delay is greater than 0
Fan Runtime Limit 0 hours 0 to 9,000 hours
Fan Runtime Reset* No Yes or No
* When Fan Runtime Limit is greater than
0
Supply Air Temperature Alarm Offset 0°F 0 to 10°F (0 to 5.5°C)
Supply Air Temperature Alarm Delay
(when Supply Air Temp Alarm Offset
is greater than 0)
300 seconds 300 to 3,600 seconds
Unocc Low Speed Fan Disable Enable or Disable
*When Fan Type = Multi-Speed Fan
(only available in versions 3.0.4 or
greater)
Inputs
BI1 Config Disabled Disabled, Open Window, Open Door, Fan
Lock, Service, Dirty Filter, Motion NC,
Motion NO, Temp Occ, Occupancy
BI2 Config Disabled Disabled, Open Window, Open Door, Fan
Lock, Service, Dirty Filter, Motion NC,
Motion NO, Temp Occ, Occupancy
Supply Temp Sensor* Nickel Nickel, Platinum, A99B, 2.25k ohm
negative temperature coefficient (NTC),
10k ohm NTC, 10k ohm NTC Type 3
* Analog and non-four pipe units
Supply Temp Offset* 0 degrees -5 to 5 degrees (°F or °C based on Units
setting under Display Settings menu)
* Analog Sensor
Zone Temp Sensor* Nickel Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
* Analog Sensor
Zone Temp Sensor Offset 0 degrees -5 to 5 degrees (°F or °C based on Units
setting under Display Settings menu)
Humidity Offset 0% RH -15% to 15% RH
Reset Sensors False True or False
Zone Temp Alarm Enabled No Yes or No
Table 10: Menus and Submenus (Part 3 of 8)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1