Install Instructions
Table Of Contents
- Applications
- North American Emissions Compliance
- United States
- Canada
- Installation
- Parts Included
- Location Considerations
- Installing the Thermostat Controller
- Wiring
- Setup and Adjustments
- Overview
- Customizing the Home Screen
- Touchscreen Icons
- User Lockout
- Using the USB Port
- Loading the Firmware
- Backing Up the Settings
- Restoring the Settings
- Choosing the Communication Mode (TEC3620-00-000, TEC3621-00-000, TEC3622-00-000, and TEC3623-00-000 Models)
- Configuring the Thermostat Controller
- Installer Configuration Menu
- Screen Reset
- Selecting the Unit Type
- By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or Pressure-Dependent VAV mode:
- Configuring the Supply Fan - Fan Coil Only
- Setting the Control Mode
- Setting the Fan Mode - Fan Coil Only
- Configuring the Zone Space or Equipment Size
- Changeover
- Dehumidification Control - Fan Coil Only
- Temperature Setpoints
- Configuring Occupancy
- Selecting Schedule Source
- Scheduling
- Setting the Local Schedule
- Overriding the Occupancy Mode
- Enabling Optimal Start
- Enabling the Motion Sensor (TEC3x21-00-000, TEC3x23-00-000 Models)
- PID/PRAC+ Automatic Control Tuning
- Configurable Binary Inputs
- Aux Control
- Commissioning Mode
- Sensor Priority
- Available Fault Diagnostics
- Menus and Submenus
- Troubleshooting
- Repair Information
- TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 2)
TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
35
Control Setup
(Cont)
Zone Temp Alarm Enabled No Yes or No
Zone Temp Low Limit 55°F 32 to 150°F (0 to 65.56°C)
Zone Temp High Limit 90°F 32 to 150°F (0 to 65.56°C)
Tuning
Temp Control Setup Automatic PID
Tuning
Automatic PID Tuning, Manual PID
Tuning, Deadband Override
Reset PID Tuning No Yes or No
Deadband* 0.7 to 1.5°F 1.0°F (-17.22 °C)
*Functionally, this is the PID deadband
when the Temp Control Setup is equal to
the Deadband Override or Manual PID
Tuning. When the Temp Control Setup
equals the On/Off Control, the Deadband
is used for the On/Off range of the stage
equipment. This parameter is hidden
when Temp Control Setup equals
Automatic PID Tuning.
Heat Prop Band* 160°F 5 to 10°F (-15 to -1.11°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
Heat Integral Time* 729 seconds 300 to 1,600 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Heat Process Range* 40°F 10 to 100°F (-12.22 to 37.77°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
Heat Saturation Time* 600 seconds 60 to 900 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Heat Time Constant* 720 seconds 360 to 1,440 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Heat Process Dead Time* 72 seconds 20 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Heat Period* 60 seconds 30 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Cool Prop Band* 160°F 5 to 10°F (-15 to -1.11°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
Cool Integral Time* 729 seconds 300 to 1,600 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Cool Process Range* 40°F 10 to 100°F (-12.22 to 37.77°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
Cool Saturation Time* 600 seconds 60 to 900 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Table 10: Menus and Submenus (Part 4 of 8)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1