Install Instructions
Table Of Contents
- Applications
- North American Emissions Compliance
- United States
- Canada
- Installation
- Parts Included
- Location Considerations
- Installing the Thermostat Controller
- Wiring
- Setup and Adjustments
- Overview
- Customizing the Home Screen
- Touchscreen Icons
- User Lockout
- Using the USB Port
- Loading the Firmware
- Backing Up the Settings
- Restoring the Settings
- Choosing the Communication Mode (TEC3620-00-000, TEC3621-00-000, TEC3622-00-000, and TEC3623-00-000 Models)
- Configuring the Thermostat Controller
- Installer Configuration Menu
- Screen Reset
- Selecting the Unit Type
- By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or Pressure-Dependent VAV mode:
- Configuring the Supply Fan - Fan Coil Only
- Setting the Control Mode
- Setting the Fan Mode - Fan Coil Only
- Configuring the Zone Space or Equipment Size
- Changeover
- Dehumidification Control - Fan Coil Only
- Temperature Setpoints
- Configuring Occupancy
- Selecting Schedule Source
- Scheduling
- Setting the Local Schedule
- Overriding the Occupancy Mode
- Enabling Optimal Start
- Enabling the Motion Sensor (TEC3x21-00-000, TEC3x23-00-000 Models)
- PID/PRAC+ Automatic Control Tuning
- Configurable Binary Inputs
- Aux Control
- Commissioning Mode
- Sensor Priority
- Available Fault Diagnostics
- Menus and Submenus
- Troubleshooting
- Repair Information
- TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 2)
TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
37
Equipment Setup
(Cont)
Reheat Min On Time* 180 seconds 0 to 360 second
* Reheat installed
Reheat/ Min Off Time* 180 seconds 0 to 360 seconds
* Reheat installed
Changeover
Changeover Mode* Auto Auto, Cooling, or Heating
* Non 4-Pipe units
Supply Temp Type* Analog Sensor Analog Sensor, Heating NC, Cooling NC
* Changeover Mode = Auto
Changeover Setpoint* 55°F 40 to 200°F (4 to 93°C)
* Supply temp type = analog sensor
Supply Temp Sensor* Nickel Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
* Supply temp type = analog sensor
Supply Temp Offset* 0°F -5 to 5°F (-3 to 3°C)
* Supply temp type = analog sensor
Trend EFF-ZNT — -50 to 250°F (-45.56 to 121.11°C)
EFF-SETPOINT
— 45 to 100°F (7.22 to 37.78°C)
EFF-ZNH
— 0 to 100%RH
B1 Status
— On or Off
B2 Status
— On or Off
EFF-OAT
— -50 to 250°F (-45.56 to 121.11°C)
EFF-SAT
— -50 to 250°F (-45.56 to 121.11°C)
FANSPD-S
— On or Off
HTG-O
— 0 to 100%
CLG-O
— 0 to 100%
System Status Occupancy Source Local Schedule Occupancy BI
Temp Occ BI
Temp Occ
Occ Override
Local Schedule
BAS Schedule
Occupancy Sensor
Table 10: Menus and Submenus (Part 6 of 8)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values