Product Overview
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2019 Johnson Controls. www.johnsoncontrols.com
6
TEC3000 Color Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or
N2 Networked Thermostat Controllers Catalog Page (Continued)
Technical specifications
TEC3000 Color Series Thermostat Controllers
Power requirements 19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
USB port power rating 120 to 250 mA current draw supported
Analog output rating (for TEC3x2x models) 0 to 10 VDC into 2k ohm resistance (minimum)
Relay contact
rating (for
TEC3x1x and
TEC3x3x models)
On/off or floating control (for
TEC3x1x models)
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class
2 or SELV
Fan relay output rating (for TEC3x1x and TEC3x2x
models)
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Auxiliary output rating/triac output (for TEX3x1x and
TEC3x2x models)
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Binary inputs For TEC3x1x and TEC3x2x models: Dry contact across terminal
COM to terminals BI1, BI2, or COS
For TEC3x3x models: Dry contact across terminal COM to
terminals BI1 or BI2
Analog inputs For TEC3x1x and TEC3x2x models (two AIs): Nickel, platinum,
A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
terminal COM to terminals R SEN or COS, 0-10 VDC
For TEC3x3x models (three AIs): Nickel, platinum, A99B, 2.25k
ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across terminal
COM to terminals R SEN, SAT, or OAT, 0-10 VDC
Temperature and humidity sensor type Local digital sensor
Wire size 18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter)
recommended
MS/TP network guidelines For wired models: Up to 100 devices maximum for each Network
Automation Engine (NAE); 4,000 ft (1,219 m) maximum cable length.
Refer to the MS/TP Technical Bulletin for the Metasys, FX, or
Verasys® system installed.
For wireless models: Up to 100 devices maximum for each
Network Automation Engine (NAE)
Wireless band (for wireless models) Direct-sequence spread-spectrum 2.4 GHz ISM bands
Transmission power (for wireless models) 10 mW maximum
Transmission range (for wireless models) 50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
Temperature
range
Backlit display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9°F/±0.5°C at 70.0°F/21.0°C typical calibrated
Humidity ±5% RH from 20% to 80% RH at 50°F to 90°F (10°C to 32°C)
Minimum deadband 2°F/1°C between heating and cooling
Occupancy sensor motion detection (occupancy
sensing models)
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
Ambient
conditions
Operating 32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensing
Storage -22°F to 122°F (-30°C to 50°C); 95% RH maximum, noncondensing