User Guide

V46 Pressure-Actuated Water-Regulating Valve Product Bulletin14
Table 14: Navy Type - Non-corrosive Refrigerants
Product Size (in.) Inlet and
Outlet
Service Element
Style
Shipping
Weight
lb (kg)
Seat Repair Kit Replacement Power
Element
V46CJ-2
1
1/2 Sweat
Connector
All Range 34 3.6 (1.6) STT15A-603R
1
SEP13A-600R
1
V46CN-2
1
3/4 4 Hole
Navy Flange
All Range 34 7.1 (3.2) STT17A-613R SEP13A-603R
V46CP-2
1
14 Hole
Navy Flange
All Range 34 12.0 (5.4) STT17A-611R
1
SEP50A-600R
V46CQ-2
1
1-1/4 4 Hole
Navy Flange
All Range 34 10.3 (4.7) STT17A-612R SEP50A-600R
V46BR-2
1
1-1/2 6 Hole Navy
Flange
All Range 34 13.5 (6.1) STT17A-612R SEP50A-600R
V46CR-2
1
1-1/2 6 Hole Navy
Flange
All Range 34 13.8 (6.3) STT17A-612R SEP50A-600R
V46BS-3
1
2 6 Hole Navy
Flange
Low Range 34 25.5
(11.6)
STT18A-602R SEP50A-601R
1
V46CS-3
1
2 6 Hole Navy
Flange
Low Range 34 24.4
(11.1)
STT18A-602R SEP50A-601R
1
V46CS-4
1
2 6 Hole Navy
Flange
High Range 34 24.4
(11.1)
STT18A-602R SEP50A-601R
1
V46BT-3
1
2-1/2 6 Hole Navy
Flange
Low Range 34 29.5
(13.4)
STT18A-602R SEP50A-601R
1
V46CT-3
1
2-1/2 6 Hole Navy
Flange
Low Range 34 25.5
(11.6)
STT18A-602R SEP50A-601R
1
V46CT-4
1
2-1/2 6 Hole Navy
Flange
High Range 34 25.5
(11.6)
STT18A-602R SEP50A-601R
1
1. Non-stock item, built to order.
Table 15: Pressure Range Specifications
Refrigerant Maximum Opening
Point, psig (kPa)
1
Modulation Start
Point, psig (kPa)
1
Maximum Permissible Pressure
psig (kPa)
V46A, B, C, D V46N Water Refrigerant
All Range R12, R22,
R134a, R502, R404a, R507
70 to 260 (483 to 1,793) 90 to 280 (621 to 1,931)
40 to 100 (276 to 690)
2
150 (1,034) 320 (2,206)
All Range with High
Overpressure
70 to 260 (483 to 1,793) 150 (1,034) 370 (2,551)
3/8 in. Extended All Range 70 to 300 (483 to 2,068) 150 (1,034) 440 (3,034)
2 and 2-1/2 in. Low Range
R12, R134a
70 to 170 (483 to 1,172) 100 to 200
(690 to 1,379)
150 (1,034) 230 (1,586)
2 and 2-1/2 in. High Range
R22, R502, R404a, R507
160 to 260
(1,103 to 1,793)
180 to 280
(1241 to 1,931)
150 (1,034) 320 (2,206)
Ammonia
R717
100 to 200
(690 to 1,379)
130 to 230
(896 to 1,586)
150 (1,034) 320 (2,206)
1. V46A, B, C direct acting valve ranges indicate the valve opening point. V46N reverse acting valve ranges indicates the
modulation start point.
2. For heat pump applications (3/8 in. through 1-1/2 in. sizes only).