Submittal Sheet
Table Of Contents
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1924165
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
© 12/02 Johnson Controls, Inc
1/1
vva802xs p;w 1924165 9thcc:4-110 Valves Electric Valves and Actuators Rev:
071897
logo:
standard
left ft:
undefnd
right ft:
standard
Sect# = 2
seQ# = 381
VA-8020-1
Floating/Incremental Control Electric Valve Actuator
va8122.tif
Description
The VA-8020-1 is a synchronous,
force-sensor-limited actuator that provides
floating/incremental control for 1/2 and 3/4 in.
valves in many HVAC applications. The
VA-8020-1 is a motor-driven, non-spring
return electric valve actuator.
Features
• provides floating/incremental control from a
three-wire, nominal 24 VAC input signal
• simplified setup and adjustment
procedures reduce installation costs
• provides 22 lb (98 N) minimum shutoff force
• compact assembly fits most unit vent and
baseboard applications
Applications
VG7000 Series
must be factory
mounted (no linkage kit required)
To Order
Specify code number VA-8020-1. Also refer
to Electric Valve and Actuator Selection
Charts. For VG7000 options, refer to
VG7000 Series Bronze Control Valves –
Adding an Electric Actuator.
Accessories
Repair Parts
Code Number Description
VA-8000-102 Valve Position Indicator
VA-8020-100
Field Mounting Kit for VT Series
Valves
Code Number Description
VA-8020-601 Replacement Cover Kit
VA-8020-605
(a)
(a) One stem retainer and clip kit is included with
each VA-8020-1 Electric Valve Actuator. If the
VA-8020-605 is ordered separately, it must be
ordered in multiples of five.
Stem Retainer and Clip Kit
Specifications
VA-8020-1 Floating/Incremental Control Electric Valve Actuator
Power Requirements
20 to 30 VAC at 50/60 Hz;
3.4 VA Supply Minimum, Class 2
Input Signal 20 to 30 VAC at 50/60 Hz, Three-Wire
Input Impedance 250 ohms Nominal
Stroke Time
(5/16 in. Stroke)
50 Hz Approximately 108 Seconds Nominal
60 Hz Approximately 90 Seconds Nominal
Shutoff Force 22 lb (98 N) Minimum
Ambient
Conditions
Operating
35 to 150°F (2 to 65°C);
85°F (30°C) Maximum Dew Point at 90% RH, Noncondensing
Storage
-40 to 150°F (-40 to 65°C);
85°F (30°C) Maximum Dew Point at 90% RH, Noncondensing
Valve Media
Temperature
Water 195°F (90°C) Maximum
Steam Actuator Not Rated for Steam
Dimensions (H x W x D) 4-1/2 in. x 5 in. x 2-1/2 in. (114 mm x 127 mm x 64 mm)
Agency Listings
UL 873 Recognized, File E27734, Guide XAPX2 (Suitable for Plenum Use);
CSA C22.2 No. 130 Certified, File LR85083, Class 3221 02
Shipping Weight 1.6 lb (0.74 kg)