Brochure
Table Of Contents
VA9203-xxx-xx Series Electric Spring Return Valve Actuators Product Bulletin 9
Technical Specifications
VA9203-GGx-2Z Series Proportional Electric Spring Return Actuator (Part 1 of 2)
Power Requirements AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety
Extra-Low Voltage (SELV) (Europe), 4.7 VA Running, 2.7 VA Holding Position
DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe)
1.8 W Running, 1 W Holding Position
Minimum Transformer Size: 6 VA per Actuator
Input Signal/Adjustments Factory Set at DC 0 to 10 V, CW Rotation with Signal Increase
Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with Field -Furnished 500 ohm
0.25 W Minimum Resistor
Switch Selectable Direct or Reverse Action with Signal Increase
Control Input Impedance Voltage Input: 100,000 ohm
Current Input: 500 ohm with Field-Furnished 500 ohm Resistor
Feedback Signal DC 0 (2) to 10 V for Desired Rotation Range up to 95°
Corresponds to Rotation Limits, 0.5 mA at 10 V Maximum
Auxiliary Switch
Rating
-xxB Models One Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver
Contacts:
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Spring Return Direction is Selectable with Mounting Position of Actuator:
Actuator Face Labeled A is Away from Valve: CCW Spring Return
Actuator Face Labeled B is Away from Valve: CW Spring Return
Rated Torque Power On
(Running)
27 lb·in (3 N·m) All Operating Temperatures
Power Off
(Spring Returning)
27 lb·in (3 N·m) All Operating Temperatures
Rotation Range Maximum Full Stroke: 95°
Adjustable Stop: 35° to 95° Maximum Position
Rotation Time for
90 Degrees of
Travel
Power On
(Running)
90 Seconds Constant for 0 to 27 lb·in. (3 N·m) Load, at all Operating
Conditions
Power Off
(Spring Returning)
12 to 17 Seconds for 0 to 27 lb·in. (3 N·m) Load, at Room Temperature
16 Seconds Nominal at Full Rated Load
22 Seconds Maximum with 27 lb·in. (3 N·m) Load, at -22°F (-30°C)
Life Cycles 60,000 Full Stroke Cycles with 27 lb·in. (3 N·m) Load
1,500,000 Repositions with 27 lb·in. (3 N·m) Load
Audible Noise
Rating
Power On
(Running)
<37 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Power On
(Holding)
<20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
<56 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical
Connections
-GGA-2Z Models 120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG
(0.75 mm
2
) Conductors and 1/4 in. (6 mm) Ferrule Ends
-GGB-2Z Models 48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG
(0.85 mm
2
) Conductors and 1/4 in. (6 mm) Ferrule Ends
Conduit Connections Integral 1/2 in. (13 mm) Threaded Conduit Connector(s)