VA9208-xxx-xx Series Electric Spring Return Actuators (Continued)
Selection Chart
Technical Specifications
VA9208-xxx-x Series Electric Spring Return Valve Actuator Models
Code Number Rotation
Time (sec)
For 90° Power
Requirement
Power
Consumption
Input Signal Position
Feedback
Auxiliary
Switches
Electrical
Connection
Power On (Running)
Power Off (Spring Return)
24 VAC +/- 25% VDC +20%/-10%
24 VAC +/- 20% VDC +20%/-10%
120 VAC +/- 10%
230 VAC +/- 10%
VA Rating, Transformer Sizing
VA: Running (Holding)
Amperage: Running (Holding)
On/Off
Floating Point
0(2) to 10 VDC
0(4) to 20 mA (with 500 ohm resistor)
0(2) to 10 VDC
2 SPDT, 5.0 A (2.9 A Inductive) at 240 V
48 in. (1.2 m) 18 AWG Appliance Cable
120 in. (3.05 m) 19 AWG Plenum Cable
Integral 3/8 in. FMC Connectors
VA9208-AGA-2 150
17 to 25
1
1. 22 seconds nominal at room temperature and rated load, 94 seconds maximum at rated load and -40°F (-40°C).
X87.9
(5.5)
XX X X
VA9208-AGA-3 150
17 to 25
1
X87.9
(5.5)
XX X X
VA9208-AGC-3 150
17 to 25
1
X87.9
(5.5)
XX X X X
VA9208-BGA-3 55 to 71
13 to 26
2
2. 21 seconds nominal at room temperature and rated load, 39 seconds maximum at rated load and -4°F (-20°C), 108 seconds maximum at 53 lb·in (6 N·m) and -
40°F (-40°C).
X 7 6.1
(1.2)
XXX
VA9208-BGC-3 55 to 71
13 to 26
2
X 7 6.1
(1.2)
XXXX
VA9208-BAA-3 55 to 71
13 to 26
2
X 0.05
(0.03)
XXX
VA9208-BAC-3 55 to 71
13 to 26
2
X 0.05
(0.03)
XXXX
VA9208-BDA-3 55 to 71
13 to 26
2
X 0.04
(0.03)
XXX
VA9208-BDC-3 55 to 71
13 to 26
2
X 0.04
(0.03)
XXXX
VA9208-GGA-2 150
17 to 25
1
X87.9
(5.5)
XX XX
VA9208-GGA-3 150
17 to 25
1
X87.9
(5.5)
XX XX
VA9208-GGC-3 150
17 to 25
1
X87.9
(5.5)
XX XXX