VG1000 Series Forged Brass Ball Valves Product Bulletin38
1 (DN25) VG1241Cx
VG1245Cx
VG1841Cx
VG1845Cx
VG1271Cx
VG1275Cx
VG1871Cx
VG1875Cx
VG1291Cx
VG1295Cx
VG1891Cx
VG1895Cx
VA9104 None Required
(Fluid Temperature
212°F)
M9000-341
M9000-561
(Fluid Temperature
284°F)
M9104 M9000-551
M9106 M9000-520
M9108 M9000-516 M9000-330
VA9203 None Required
(Fluid Temperature
212°F)
M9000-341
M9000-561
(Fluid Temperature
284°F)
1-1/4
(DN32)
VG1241Dx
VG1245Dx
VG1841Dx
VG1845Dx
M9106 M9000-520
M9108 M9000-516 M9000-330
VA9208 None Required
(Fluid Temperature
212°F)
M9000-341
M9000-561 (Fluid
Temperature
284°F)
1-1/2
(DN40)
VG1241Ex
VG1245Ex
VG1841Ex
VG1845Ex
M9106 M9000-520
M9108 M9000-516 M9000-330
VA9208 None Required
(Fluid Temperature
212°F)
M9000-341
M9000-561 (Fluid
Temperature
284°F)
2 (DN50) VG1241Fx
VG1245Fx
VG1841Fx
VG1845Fx
M9109 M9000-520
M9108 M9000-516 M9000-330
VA9208 None Required
(Fluid Temperature
212°F)
M9000-341
M9000-561 (Fluid
Temperature
284°F)
1. VA9104, M9104, M9106, M9108, M9109 and M9106 Series Actuators are non-spring return; and VA9203 and VA9208 Series
Actuators are spring return. Note: VA9104, M9104, VA9203, and VA9208 have a maximum fluid temperature limit of 212°F
(100°C). The VA9104, M9104, VA9203, and VA9208 temperatures can be increased to 284°F (140°C) or 15 psi steam with
the addition of the M9000-561 thermal barrier.
2. To avoid excessive wear or drive time on the motor for VA9104, M9104, M9106, and M9109 AGx models, use a controller
and/or software that provides a timeout function to remove the signal at the end of rotation (stall). The IGx and GGx models
have an automatic shutoff to avoid excessive wear or drive time on the motor.
Table 32: Valid Ball Valve, Electric Actuator, Linkage Kit, and Weather Shield Combinations (for Assembly
in the Field) (Part 2 of 2)
Valve Size,
in. (DN)
Valve Code Numbers Actuator
Base
Number
1
Linkage Kit
Code Number
Weather Shield
NPT End
Connection
Sweat End
Connection
Press End
Connection