Brochure

VG1000 Series Forged Brass Ball Valves Product Bulletin 5
Table 4: Two-Way Stainless Steel Trim Ball Valves, Non-Spring Return, VA9104 Actuators without
Switches
Fluid Temperatures:
-4 to 212°F (-20 to 100°C)
Not Rated for Steam Service
AC 24 V
On/Off (Floating)
without Timeout
1
On/Off (Floating)
with Timeout
0 to 10 VDC
Proportional
Valve Size,
in.
Cv Closeoff
psig
Actuators with M3 Screw Terminals VA9104-AGA-3S VA9104-IGA-3S VA9104-GGA-3S
VG1245AD 1/2 1.2
2
200 VG1245AD+9T4AGA VG1245AD+9T4IGA VG1245AD+9T4GGA
VG1245AE 1.9
2
VG1245AE+9T4AGA VG1245AE+9T4IGA VG1245AE+9T4GGA
VG1245AF 2.9
2
VG1245AF+9T4AGA VG1245AF+9T4IGA VG1245AF+9T4GGA
VG1245AG 4.7
2
VG1245AG+9T4AGA VG1245AG+9T4IGA VG1245AG+9T4GGA
VG1245AL 7.4
2
VG1245AL+9T4AGA VG1245AL+9T4IGA VG1245AL+9T4GGA
VG1245AN 11.7 VG1245AN+9T4AGA VG1245AN+9T4IGA VG1245AN+9T4GGA
VG1245BG 3/4 4.7
2
200 VG1245BG+9T4AGA VG1245BG+9T4IGA VG1245BG+9T4GGA
VG1245BL 7.4
2
VG1245BL+9T4AGA VG1245BL+9T4IGA VG1245BL+9T4GGA
VG1245BN 11.7 VG1245BN+9T4AGA VG1245BN+9T4IGA VG1245BN+9T4GGA
VG1245CL 17.4
2
200 VG1245CL+9T4AGA VG1245CL+9T4IGA VG1245CL+9T4GGA
VG1245CN 11.7
2
VG1245CN+9T4AGA VG1245CN+9T4IGA VG1245CN+9T4GGA
VG1245CP 18.7 VG1245CP+9T4AGA VG1245CP+9T4IGA VG1245CP+9T4GGA
Actuators with 120 in. (3.05 m) 18 AWG
Plenum Cable
VA9104-AGA-2S VA9104-IGA-2S VA9104-GGA-2S
VG1245AD 1/2 1.2
2
200 VG1245AD+9A4AGA VG1245AD+9A4IGA VG1245AD+9A4GGA
VG1245AE 1.9
2
VG1245AE+9A4AGA VG1245AE+9A4IGA VG1245AE+9A4GGA
VG1245AF 2.9
2
VG1245AF+9A4AGA VG1245AF+9A4IGA VG1245AF+9A4GGA
VG1245AG 4.7
2
VG1245AG+9A4AGA VG1245AG+9A4IGA VG1245AG+9A4GGA
VG1245AL 7.4
2
VG1245AL+9A4AGA VG1245AL+9A4IGA VG1245AL+9A4GGA
VG1245AN 11.7 VG1245AN+9A4AGA VG1245AN+9A4IGA VG1245AN+9A4GGA
VG1245BG 3/4 4.7
2
200 VG1245BG+9A4AGA VG1245BG+9A4IGA VG1245BG+9A4GGA
VG1245BL 7.4
2
VG1245BL+9A4AGA VG1245BL+9A4IGA VG1245BL+9A4GGA
VG1245BN 11.7 VG1245BN+9A4AGA VG1245BN+9A4IGA VG1245BN+9A4GGA
VG1245CL 17.4
2
200 VG1245CL+9A4AGA VG1245CL+9A4IGA VG1245CL+9A4GGA
VG1245CN 11.7
2
VG1245CN+9A4AGA VG1245CN+9A4IGA VG1245CN+9A4GGA
VG1245CP 18.7 VG1245CP+9A4AGA VG1245CP+9A4IGA VG1245CP+9A4GGA
1. To avoid excessive wear or drive time on the motor for the AGx models, use a controller or software that provides a timeout function to remove the signal at the
end of rotation (stall).
2. Cv has a characterizing risk.