Brochure

VG1000 Series Forged Brass Ball Valves Product Bulletin42
See Figure 11 for dimensions of the VA9203 Spring
Return Series Actuated VG1241, VG1245, VG1841,
and VG1845 Series NPT End Connection Ball Valves
with optional M9000-561 Thermal Barrier installed. See
Table 38 for specific model linkage dimensions.
Table 38: VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valve with Optional
Thermal Barrier Installed Dimensions, in. (mm)
Valve Size
in. (DN)
1
ABCDEFG
1/2 (DN15) 6 (152) 21/32 (17) 1-7/32 (31) 6-31/32 (177) 2-33/64 (64) 11/32 (9) 1-1/4 (32)
3/4 (DN20) 6 (152) 21/32 (17) 1-7/32 (31) 7-1/8 (181) 2-51/64 (71) 11/32 (9) 1-13/32 (36)
1 (DN25) 6-1/16 (154) 3/4 (19) 1-19/64 (33) 7-31/64 (190) 3-13/32 (87) 11/32 (9) 1-45/64 (43)
1. Port A must always be connected to the coil.
Figure 11: Spring Return VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with
Optional M9000-561 Thermal Barrier Installed Dimensions, in. (mm)
Port Marking
Locations
F
I
G
:
V
A
9
2
0
3
X
_
d
i
m
s
t
h
b
r
2-7/8
(73)
3-1/4
(82)
A
D
3-1/2 (89)
Clearance Required