Selection Guide

Non-Spring Return Electric Actuators
NPT Connections
Standard or High Fluid Temperature Range
Brass or Stainless Steel Trim
200 PSID Close Off Pressure
Fluid Temperature Limits:
Brass Trim: 23 to 203°F (-5 to 95°C)
Stainless Steel Trim: -22 to 284°F (-30 to 140°C)
Non-Spring
Return
M9108
On / Off
and Floating Point
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
1 SPDT, 5.0(2.9) A @ 240 V
Auxiliary Switches: 2 SPDT, 5.0(2.9) A @ 240 V
2 SPDT, 3.0(1.5) A @ 24 VAC
Inch
DN
(mm)
Cv
1
2-Way
Brass Trim
3-Way
Brass Trim
2-Way
Stainless Steel Trim
3-Way
Stainless Steel Trim
1/2 15
1.2 (0.7) VG1241AD VG1841AD VG1245AD VG1845AD
1.9 (1.2) VG1241AE VG1841AE VG1245AE VG1845AE
2.9 (1.9) VG1241AF VG1841AF VG1245AF VG1845AF
4.7 (2.9) VG1241AG VG1841AG VG1245AG VG1845AG
7.4 (4.7) VG1241AL VG1841AL VG1245AL VG1845AL
11.7 (5.8) VG1241AN VG1841AN VG1245AN VG1845AN
3/4 20
4.7 (2.9) VG1241BG VG1841BG VG1245BG VG1845BG
7.4 (4.7) VG1241BL VG1841BL VG1245BL VG1845BL
11.7 (5.8) VG1241BN VG1841BN VG1245BN VG1845BN
1 25
7.4 (4.7) VG1241CL VG1841CL VG1245CL VG1845CL
11.7 (7.4) VG1241CN VG1841CN VG1245CN VG1845CN
18.7 (9.4) VG1241CP VG1841CP VG1245CP VG1845CP
1 1/4 32
11.7 (7.4) VG1241DN VG1841DN VG1245DN VG1845DN
18.7 (11.7) VG1241DP VG1841DP VG1245DP VG1845DP
29.2 (14.6) VG1241DR VG1841DR VG1245DR VG1845DR
1 1/2 40
18.7 (11.7) VG1241EP VG1841EP VG1245EP VG1845EP
29.2 (18.7) VG1241ER VG1841ER VG1245ER VG1845ER
46.8 (23.4) VG1241ES VG1841ES VG1245ES VG1845ES
2 50
29.2 (18.7) VG1241FR VG1841FR VG1245FR VG1845FR
46.8 (29.2) VG1241FS VG1841FS VG1245FS VG1845FS
73.7 (36.8) VG1241FT VG1841FT VG1245FT VG1845FT
VALVE CODE ACTUATOR CODE
(For Field Assembly)
M9108-AGA-2
M9108-AGC-2
M9108-GGA-2
M9108-GGC-2
Position Feedback:
0(2) to 10 VDC Position Feedback
Power Requirements:
24 VAC +25%/-20%, Class 2, SELV
24 VAC +25%/-15%, VDC +/- 10%
24 VAC +/- 20%, VDC +/- 10%
24 VAC +/- 25%, VDC +/- 10%
120 VAC +10%/-15% at 60 Hz
85 to 264 VAC at 50/60 Hz
Electrical Connections:
Screw Terminals
48 in. (1.2 m) 19 AWG Plenum Cable
120 in. (3.05 m) 19 AWG Plenum Cable
1/4 in. Spade Terminals
48 in. (1.2 m) 18 AWG Appliance Cable
Weather Shield Options (For Field Assembly Only)
M9000-330 Weather Shield + M9000-516 Linkage
1 For 3-Way valves, the first Cv listed is for Port A (Coil). The second Cv listed in parenthesis is for Port B (Bypass).
Actuator Type
Valve Type Actuator
Options
Control Input
Additional Actuator and Accessory Reference Information
Special Configurations:
Field Assembled
Weather Applications
Field Assembled M9108
Actuator, M9000-516
Linkage and M9000-330
Weather Shield on NPT
Threaded Ball Valve
Valve Size
in. (mm)
NPT End
Connection
Sweat End
Connection
Press End
Connection
Actuator
Base Code
Number
1
Linkage Kit Code Number Weather Shield Code Number
1/2 (DN15)
VG1241Ax
VG1245Ax
VG1841Ax
VG1845Ax
VG1275Ax
VG1875Ax
VG1295Ax
VG1895Ax
VA9104
2
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9104
2
M9000-551 (Fluid Temperatures <212°F)
M9000-551 and M9000-561 (Fluid Temperatures >212°F)
M9106
2
M9000-520
M9108 M9000-516 M9000-330
VA9203
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9203
M9000-560 (Fluid Temperatures <212°F)
M9000-560 and M9000-561 (Fluid Temperatures >212°F)
3/4 (DN20)
VG1241Bx
VG1245Bx
VG1841Bx
VG1845Bx
VG1275Bx
VG1875Bx
VG1295Bx
VG1895Bx
VA9104
2
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9104
2
M9000-551 (Fluid Temperatures <212°F)
M9000-551 and M9000-561 (Fluid Temperatures >212°F)
M9106
2
M9000-520
M9108 M9000-516 M9000-330
VA9203
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9203
M9000-560 (Fluid Temperatures <212°F)
M9000-560 and M9000-561 (Fluid Temperatures >212°F)
1 (DN25)
VG1241Cx
VG1245Cx
VG1841Cx
VG1845Cx
VG1275Cx
VG1875Cx
VG1295Cx
VG1895Cx
VA9104
2
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9104
2
M9000-551 (Fluid Temperatures <212°F)
M9000-551 and M9000-561 (Fluid Temperatures >212°F)
M9106
2
M9000-520
M9108 M9000-516 M9000-330
VA9203
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9203
M9000-560 (Fluid Temperatures <212°F)
M9000-560 and M9000-561 (Fluid Temperatures >212°F)
1 1/4
(DN32)
VG1241Dx
VG1245Dx
VG1841Dx
VG1845Dx
M9106
2
M9000-520
M9108 M9000-516 M9000-330
VA9208
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9208
M9000-560 (Fluid Temperatures <212°F)
M9000-560 and M9000-561 (Fluid Temperatures >212°F)
1 1/2
(DN40)
VG1241Ex
VG1245Ex
VG1841Ex
VG1845Ex
M9106
2
M9000-520
M9108 M9000-516 M9000-330
VA9208
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9208
M9000-560 (Fluid Temperatures <212°F)
M9000-560 and M9000-561 (Fluid Temperatures >212°F)
2 (DN50)
VG1241Fx
VG1245Fx
VG1841Fx
VG1845Fx
M9109
2
M9000-520
M9108 M9000-516 M9000-330
VA9208
Non-required (Fluid Temperatures <212°F)
M9000-341
(When using Weather Shield
M9000-561 Thermal Barrier is
not needed)
M9000-561 (Fluid Temperatures >212°F)
M9208
M9000-560 (Fluid Temperatures <212°F)
M9000-560 and M9000-561 (Fluid Temperatures >212°F)
Flanged Ball Valves, ASME Class 150 Flange
2 1/2
(DN65)
VG12A5Gx M9124 M9000-518 M9000-330
VG18A5Gx M9220
M9000-519
M9000-340
3 (DN80)
VG12A5Hx M9124 M9000-518 M9000-330
VG18A5Hx M9220
M9000-519
M9000-340
4 (DN100)
VG12A5Jx M9124 M9000-518 M9000-330
VG18A5Jx M9220
M9000-519
M9000-340
Valid Field Assembly Combinations
VG1000 Series Ball Valves, M(VA)9000 Series Actuators, Linkage Kits, Weather Shields
1 The VA9104, M9104, M9106, M9108, M9109 and M9124 are non-spring return models. The VA9203, VA9208 and M9220 are spring return models.
2 To avoid excessive wear or drive time on the motor for VA9104, M9104, M9106 and M9109 AGx models, use a controller and/or software that provides a timeout
function to remove the signal at the end of rotation (stall). The IGx and GGx models have an auto shutoff to avoid excessive wear or drive time on the motor
11 vg1000 selection guide vg1000 selection guide 12
SPECIAL CONFIGURATIONS: NON-SPRING RETURN ACTUATORS FOR WEATHER SHIELD APPLICATIONS