Brochure

VG1000 Series Forged Brass Ball Valves Product Bulletin4
See Table 3 to determine the correct factory-mounted
actuator, where needed.
Table 3: Ordering Data – Adding a Factory-Mounted Electric Actuator
1
V G1 241AE+ Actuator + = Factory-Mounted Actuator
H = High Temperature Linkage (VA9104, VA9203, and VA9208 actuators)
9 Mounting (Leave Fields 9 through 15 blank for valve without factory-mounted actuator.)
9 Actuator 9 = Direct Acting M9000 or VA9000 Series Actuator
10 Series
0 6 Actuator Size
2
06 = M9106-xGx-2 (1/2, 3/4, 1, 1-1/4, and 1-1/2 in. NPT Valves)
11 12 . 09 = M9109-xGx-2 (2 in. Valves Only)
23 = VA9203-xxx-2(Z) Spring Opens
28 = VA9208-AGA-2 and VA9208-GGA-2 Spring Opens
43 = VA9203-xxx-2(Z) Spring Closes
48 = VA9208-AGA-2 and VA9208-GGA-2 Spring Closes
38 = VA9208-xxx-3 Spring Opens (available in AGC, BAA, BAC, BGA, BGC,
and GGC)
58 = VA9208-xxx-3 Spring Closes (available in AGC, BAA, BAC, BGA, BGC,
and GGC)
A4 = VA9104-xGA-2S, Non-Spring Return, 120 in. Cable
(All 1/2, 3/4, and 1 in. Valves)
T4 = VA9104-xGA-3S, Non-Spring Return, Screw Terminals
(All 1/2, 3/4, and 1 in. Valves)
G Control Type A = Floating, AC/DC 24 V Input (VA9104, M9106, M9109, VA9203, and
VA9208)
13 B = On/Off (VA9203 and VA9208)
G = Prop. DC 0 (2) to 10 V or 0 (4) to 20 mA (M9106, M9109, VA9104,
VA9203, and VA9208)
I = On/Off Floating with Timeout (VA9104, M9106, and M9109)
G Supply A = AC 120 V (VA9208-BAx Only)
14 Voltage G = 24 VAC (All Models)
U = AC 85 to 264 V (VA9203-BUx Only)
C Auxiliary Switch A = No Auxiliary Switch (All models)
B = One Auxiliary Switch
C = Two Auxiliary Switches
15
1 234567891011 12 13 14 15 = Field
V G1 241AE+9 0 6GG C Example: Forged brass ball valve, two-way, threaded (NPT), brass trim, equal %, 1/2 in.
(DN15) 1.9 Cv, factory-mounted direct acting M9106-GGC-2 Actuator, non-spring
return, proportional control, AC 24 V supply (with feedback), and two-way auxiliary
switches
Valve + Actuator
1. Before retrofitting older valves with VA9104, M9104, VA9203, or VA9208 actuators, be sure that the valves have a tapped
hole in the center of the valve stem and no threads in the flange holes. These direct mount actuators do not fit older valves
designed without a tapped center stem hole or with threaded flange mounting holes.
2. Refer to actuator product bulletin for detailed information.