Actuator Install Instructions
Table Of Contents
Published in U.S.A. www.johnsoncontrols.com
VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions  11
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Life Cycles 60,000 Full Stroke Cycles with 70 lb·in. (8 N·m) Load
Audible Noise 
Rating
Power On
(Running)
<47 dBA at 70 lb·in. (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Power On
(Holding)
<20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
<52 dBA at 70 lb·in. (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical 
Connections
Bxx-3 Models 48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG 
(0.85 mm
2
) Conductors and 1/4 in. (6 mm) Ferrule Ends
Auxiliary Switches
(-xxC Models)
48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG 
(0.85 mm
2
) Conductors and 1/4 in. (6 mm) Ferrule Ends
Conduit Connections Integral Connectors for 3/8 in. (10 mm) Flexible Metal Conduit
Fluid 
Temperature 
Limits
VG12x1 and VG18x1 
Series
23 to 203°F (-5 to 95°C), Not Rated for Steam Service
VG12x5 and VG18x5 
Series
-22 to 212°F (-30 to 100°C), Not Rated for Steam Service
VG12x5 and VG18x5 
Series with 
M9000-561 Thermal 
Barrier Installed
-22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) 
Saturated Steam
Ambient 
Conditions
Standard Operating -4 to 140°F (-20 to 60°C); 90% RH Maximum, Noncondensing
Extended Operating -40 to 4°F (-40 to -20°C); 90% RH Maximum, Noncondensing
Storage -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
Enclosure Rating NEMA 2 (IP54) for all Mounting Directions
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, 
Automatic Electrical Controls for Household and Similar Use; and 
UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for Electric 
Actuators
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 
3rd Ed., Automatic Electrical Controls for Household and Similar Use; and 
CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance 
with the essential requirements and other relevant provisions of the 
EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC.
Australia and New 
Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight -BGC Models 3.8 lb (1.7 kg)
-BAC and -BDC 
Models
4.2 lb (1.9 kg)
-BGA Models 3.4 lb (1.5 kg)
-BAA and -BDA 
Models
3.8 lb (1.7 kg)
VA9208-Bxx-x Series On/Off Electric Spring Return Actuator (Part 2 of 2)