Selection Guide

Ball Valves with
VA9104 Series
Actuators
Ball Valves with
M9106(9) Series
Actuators
Ball Valves with
VA9203 Series
Actuators
Ball Valves with
VA9208 Series
Actuators
Motorized Ball
Valve Assembly
with Weather
Shield
(field assembly)
NPT Threaded
Standard Fluid Temperature Range
Brass or Stainless Steel Trim
200 PSID Close Off Pressure
Fluid Temperature Limits:
Brass Trim: 23 to 203°F (-5 to 95°C)
Stainless Steel Trim: -22 to 212°F (-30 to 100°C)
Non-Spring Return Spring Return Port A Open Spring Return Port A Closed
VA9104 M9106 M9109 VA9203 VA9208 VA9203 VA9208
Floating Point
without Timeout
On / Off
and Floating Point
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
Floating Point
without Timeout
On / Off
and Floating Point
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
Floating Point
without Timeout
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
On / Off
and Floating Point
85 to 264V On / Off
24V On / Off
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
On / Off
and Floating Point
120V On / Off
24V On / Off
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
On / Off
and Floating Point
85 to 264V On / Off
24V On / Off
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
On / Off
and Floating Point
120V On / Off
24V On / Off
0 (2) to 10 VDC
0 (4) to 20 mA
(w/500 ohm resistor)
1 SPDT, 5.0(2.9) A @ 240 V
Auxiliary Switches: 2 SPDT, 5.0(2.9) A @ 240 V
2 SPDT, 3.0(1.5) A @ 24 VAC
Electrical Screw Terminals
Connections: 120 in. Plenum Cable
Inch
DN
(mm)
Cv
2
Brass Trim Stainless Steel Trim
2-Way 3-Way 2-Way 3-Way
1/2 15
1.2 (0.7) VG1241AD VG1841AD VG1245AD VG1845AD
1.9 (1.2) VG1241AE VG1841AE VG1245AE VG1845AE
2.9 (1.9) VG1241AF VG1841AF VG1245AF VG1845AF
4.7 (2.9) VG1241AG VG1841AG VG1245AG VG1845AG
7.4 (4.7) VG1241AL VG1841AL VG1245AL VG1845AL
11.7 (5.8) VG1241AN VG1841AN VG1245AN VG1845AN
3/4 20
4.7 (2.9) VG1241BG VG1841BG VG1245BG VG1845BG
7.4 (4.7) VG1241BL VG1841BL VG1245BL VG1845BL
11.7 (5.8) VG1241BN VG1841BN VG1245BN VG1845BN
1 25
7.4 (4.7) VG1241CL VG1841CL VG1245CL VG1845CL
11.7 (7.4) VG1241CN VG1841CN VG1245CN VG1845CN
18.7 (9.4) VG1241CP VG1841CP VG1245CP VG1845CP
1 1/4 32
11.7 (7.4) VG1241DN VG1841DN VG1245DN VG1845DN
18.7 (11.7) VG1241DP VG1841DP VG1245DP VG1845DP
29.2 (14.6) VG1241DR VG1841DR VG1245DR VG1845DR
1 1/2 40
18.7 (11.7) VG1241EP VG1841EP VG1245EP VG1845EP
29.2 (18.7) VG1241ER VG1841ER VG1245ER VG1845ER
46.8 (23.4) VG1241ES VG1841ES VG1245ES VG1845ES
2 50
29.2 (18.7) VG1241FR VG1841FR VG1245FR VG1845FR
46.8 (29.2) VG1241FS VG1841FS VG1245FS VG1845FS
73.7 (36.8) VG1241FT VG1841FT VG1245FT VG1845FT
MOTORIZED VALVE
=
VALVE CODE
+
FACTORY
ASSEMBLY CODE
3
ASSEMBLY CODE
Example: VG1241AD+9T4AGA
+9T4AGA
+9A4AGA
+9T4IGA
+9A4IGA
+9T4GGA
+9A4GGA
+906AGA
+906AGC
+906IGA
+906IGC
+906GGA
+906GGC
+909AGA
+909AGC
+909GGA
+909GGC
+923AGA
+923AGB
+923BUA
+923BUB
+923BGA
+923BGB
+923GGA
+923GGB
+928AGA
+938AGC
+938BAA
+938BAC
+938BGA
+938BGC
+928GGA
+938GGC
+943AGA
+943AGB
+943BUA
+943BUB
+943BGA
+943BGB
+943GGA
+943GGB
+948AGA
+958AGC
+958BAA
+958BAC
+958BGA
+958BGC
+948GGA
+958GGC
Position Feedback:
0(2) to 10 VDC Position Feedback
Power Requirements:
24 VAC +25%/-20%, Class 2, SELV
24 VAC +25%/-15%, Class 2, SELV
24 VAC +/- 20%, VDC +/- 10%
24 VAC +/- 25%, VDC +/- 10%
120 VAC +10%/-15% at 60 Hz
85 to 264 VAC at 50/60 Hz
Electrical Connections:
120 in. (3.05 m) 19 AWG Plenum Cable
1/4 in. Spade Terminals
48 in. (1.2 m) 18 AWG Appliance Cable
Weather Shield Options (For Field Assembly Only)
M9000-341
Requires M9108 Actuator! See page 11
1 VA9xxx Series Actuators are direct mount actuators, M9106 and M9109 valve/actuator assemblies include the M9000-520 linkage
2 For 3-Way valves, the first Cv listed is for Port A (Coil). The second Cv listed in parenthesis is for Port B (Bypass).
3 For ball valve and actuator factory assemblies combine valve code number and actuator valve assembly code.
Example: VG1241AD+9T4AGA is 1/2 inch two-way ball valve, 1.2 Cv, NPT end connections, plated brass trim with VA9104 Series non-spring return
electric actuator with 24 VAC floating point control without time out with screw terminal electrical connections.
Factory Assembled
Motorized Valve Assemblies
Standard Fluid Temperature Range
NPT Threaded
Actuator Type
1
Factory Assembled Valve + Actuator Combinations Matrix
Valve Type
Actuator Options
Control Input
Additional Actuator and Accessory Reference Information
3 vg1000 selection guide vg1000 selection guide 4
NPT THREADED, STANDARD FLUID TEMPERATURE RANGE