Product Overview
Table Of Contents
VG7000 Series Bronze Control Valves Product Bulletin16
Table 16: Stainless Steel Trim – Maximum Closeoff Pressures, psig (kPa) for PDTO Two-Way and PDTO
Port for Three-Way Electrically Actuated Valves
1
Not Available Factory Coupled for PDTO Two-Way — Field Mounting Only
338°F (170°C) Maximum Fluid Temperature
2
Valve
Size,
in. (DN)
1/2
(DN15)
3/4
(DN20)
1
(DN25)
1-1/4
(DN32)
1-1/2
(DN40)
2
(DN50)
Maximum
Cv (Kv)
Factor
0.73
(0.63)
1.8
(1.6)
4.6
(4.0)
7.3
(6.3)
11.6
(10.0)
18.5
(16.0)
28.9
(25.0)
46.2
(40.0)
VA-715x 308
(2,122)
308
(2,122)
161
(1,109)
96
(661)
63
(434)
36
(248)
22
(152)
14
(97)
VA-720x 308
(2,122)
308
(2,122)
308
(2,122)
197
(1,357)
131
(903)
75
(517)
46
(317)
29
(200)
VA-4233 224
(1,543)
224
(1,543)
108
(744)
64
(441)
41
(282)
24
(165)
--- ---
M9116 or
M9220
308
(2,122)
308
(2,122)
308
(2,122)
201
(1,385)
133
(916)
76
(524)
47
(324)
30
(207)
M110
3
125
(861)
125
(861)
61
(420)
36
(248)
23
(158)
13
(90)
8
(55)
5
(34)
M120 and
M130
3
308
(2,122)
308
(2,122)
164
(1,130)
98
(675)
64
(441)
37
(255)
23
(158)
14
(96)
M140
3
308
(2,122)
308
(2,122)
250
(1,723)
149
(1,027)
99
(682)
57
(393)
35
(241)
22
(152)
M150
3
308
(2,122)
308
(2,122)
308
(2,122)
273
(1,881)
182
(1,254)
104
(717)
64
(441)
40
(276)
1. The maximum closeoff pressure listed is limited to the maximum allowable ANSI valve body rating corresponding to the
maximum temperature rating (308 psig [2,122 kPa] at 338°F [170°C]) of the valve.
The maximum closeoff pressures listed are for actuators coupled to the appropriate mounting kits listed in Table 8 and
Table 10. See Table 17 and Table 18 for valid factory-mounted combinations, and Table 8 and Table 10 for available field
mounting kits.
2. The maximum fluid temperature is 338°F (170°C) water to 100 psig (690 kPa) saturated steam except for the following:
VA-4233 Actuators are limited to 35 to 250°F (2 to 121°C) water to 15 psig (103 kPa) saturated steam.
3. The M110, M120, M130, M140, and M150 Actuators are not available factory coupled to the valve body. The maximum
closeoff pressure values are provided because these actuators can be field mounted to the VG7000 valve body using the
mounting kits listed in Table 8 and Table 10.