Product Overview

Published in U.S.A. www.johnsoncontrols.com
VG7000 Series Bronze Control Valves Product Bulletin 31
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2008 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Valve Fluid Operating
Temperature Limits
Brass Trim
Valve with
Pneumatic
Actuator
For V-3801-8001 and V-3000-8003 Actuators:
35 to 248°F (2 to 120°C) Water; 15 psig (103 kPa) Saturated Steam
For MP82 and V-3000-8011 Actuators:
35 to 284°F (2 to 140°C) Water; 38 psig (262 kPa) Saturated Steam
Brass Trim
Valve with
Electric
Actuator
For VA-8x2x Actuators:
195°F (91°C) Maximum Water; Actuators are not rated for steam.
For VA-4233-xGx-2 Actuators:
35 to 250°F (2 to 121°C) Water; 15 psig (103 kPa) Saturated Steam
For All Other Electric Actuators:
35 to 284°F (2 to 140°C) Water; 38 psig (262 kPa) Saturated Steam
SS Trim
Valve with
Pneumatic
Actuator
All Pneumatic Actuators:
35 to 338°F (2 to 170°C) Water; 100 psig (690 kPa) Saturated Steam
SS Trim
Valve with
Electric
Actuator
For VA-4233-xGx-2 Actuators:
35 to 250°F (2 to 121°C) Water; 15 psig (103 kPa) Saturated Steam
For All Other Electric Actuators:
35 to 338°F (2 to 170°C) Water; 100 psig (690 kPa) Saturated Steam
Actuator Ambient Operating
Temperature Limits
For M9116/M9220 Series Electric Actuators:
The maximum ambient operating temperature is limited to 110°F (43°C)
for fluid operating temperatures greater than 285°F (141°C).
For All Other Actuators:
Refer to the appropriate actuator or linkage kit product bulletin. Ambient
operating temperature or other service limitations vary by selected
actuator.
Compliance 1/2, 3/4, and
1 in. Valves
Pressure Equipment Directive (PED) 97/23/EC:
Paragraph 3, Comma 3 (CE Marking is not applicable.)
1-1/4, 1-1/2,
and 2 in.
Valves
Pressure Equipment Directive (PED) 97/23/EC:
Category 1, Mod. A (Subject to CE Marking)
1. For models and ordering data, see Table 2, Table 3, and Table 4.
For maximum closeoff pressures, see Table 11 through Table 16.
For accessories (order separate), see Table 25.
2. Proper water treatment is recommended; refer to VDI 2035 Standard.
3. Rangeability is defined as the ratio of maximum flow to minimum controllable flow.