Install Instructions

Published in U.S.A. www.johnsoncontrols.com
VG7000 Series Bronze Control Valves Installation Instructions8
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2008 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Materials Body: Cast Bronze
Bonnet: Brass
Brass Trim Stem: Stainless Steel
Plug: Brass
Seat: Brass Against Molded Elastomeric Disk
Packing: Self-Adjusting Ethylene Propylene Rubber (EPR) Ring Pack
U-Cups
SS Trim Stem: Stainless Steel
Plug: Stainless Steel
Seat: Stainless Steel
Packing: Spring Loaded Polytetrafluoroethylene (PTFE) and
Elastomer V-Rings
Valve Fluid Operating
Temperature Limits
Brass Trim
Valve with
Pneumatic
Actuator
For V-3801-8001 and V-3000-8003 Actuators:
35 to 248°F (2 to 120°C) Water; 15 psig (103 kPa) Saturated Steam
For MP82 and V-3000-8011 Actuators:
35 to 284°F (2 to 140°C) Water; 38 psig (262 kPa) Saturated Steam
Brass Trim
Valve with
Electric
Actuator
For VA-8x2x Actuators:
195°F (91°C) Maximum Water; Actuators are not rated for steam.
For VA-4233-xGx-2 Actuators:
35 to 250°F (2 to 121°C) Water; 15 psig (103 kPa) Saturated Steam
For All Other Electric Actuators:
35 to 284°F (2 to 140°C) Water; 38 psig (262 kPa) Saturated Steam
SS Trim
Valve with
Pneumatic
Actuator
All Pneumatic Actuators:
35 to 338°F (2 to 170°C) Water; 100 psig (690 kPa) Saturated Steam
SS Trim
Valve with
Electric
Actuator
For VA-4233-xGx-2 Actuators:
35 to 250°F (2 to 121°C) Water; 15 psig (103 kPa) Saturated Steam
For All Other Electric Actuators:
35 to 338°F (2 to 170°C) Water; 100 psig (690 kPa) Saturated Steam
Actuator Ambient Operating
Temperature Limits
Refer to the appropriate actuator or linkage kit product bulletin. Ambient
operating temperature or other service limitations vary by selected
actuator.
Compliance 1/2, 3/4, and
1 in. Valves
Pressure Equipment Directive (PED) 97/23/EC:
Paragraph 3, Comma 3 (CE Marking is not applicable.)
1-1/4, 1-1/2,
and 2 in.
Valves
Pressure Equipment Directive (PED) 97/23/EC:
Category 1, Mod. A (Subject to CE Marking)
1. Proper water treatment is recommended; refer to VDI 2035 Standard.
2. Rangeability is defined as the ratio of maximum flow to minimum controllable flow.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
VG7000 Series Bronze Control Valves (Part 2 of 2)