Brochure

to one control server. You must use the gateway
and control server to connect to a BAS. If you do not
want to connect to a BAS, you can use the control
server to set schedules.
The LoRaWAN is a networking protocol designed
to wirelessly connect battery operated devices to
the Internet. The gateway converts LoRa RF packets
into IP packets and IP packets into RF packets. For
more information about LoRaWAN, visit https://lora-
alliance.org/about-lorawan/
Figure 2: Gateway
Figure 3: Control Server
Survey Kit
The WTL Survey Kit can survey larger, multi-story
sites for compatibility with the WTL Thermostat.
Use the WTL Survey Kit to perform a range test to
determine the strength of the wireless connection
between the WTL Thermostat and the WTL
Gateways at the location where you plan to install
the devices. If the signal strength is not sufficient
at the WTL Thermostat installation locations, you
may need to adjust the gateway and control server
installation location or potentially add additional
gateways to ensure sufficient wireless signal
coverage.
Features and benefits
Digital zone control
Optimizes energy usage and comfort
Programmable temperature setbacks
Automatic setpoint changes based on time-of-day
schedule and night setback to save energy
Diagnostic monitoring
Reduces maintenance and operating cost
Early problem detection
Avoids disruptions to system operation and
eliminates customer complaints
Failsafe
Maintains temperature setpoint even if battery is
dead
Integrate to a BAS
Provides dual-function operation. WTL Thermostats
can operate with wireless infrastructure and
connection to a BAS. Integrate with a BAS to log,
display, control, and view trend data from the WTL
network
Support BACnet Schedule
Supports schedule through the control server if not
integrated with BAS, or through the BAS scheduling
feature if the WTL system is connected to a BAS
Selection charts
Table 1: WTL Series selection chart
Product code Description
WTL-PD1-00 Wireless, pneumatic, direct-
acting 2-pipe thermostat for
terminal unit with one actuator.
Single setpoint temperature
control for cooling-only or
heating-only applications.
WTL-PR1-00 Wireless, pneumatic, reverse-
acting 2-pipe thermostat for
terminal unit with one actuator.
Single setpoint temperature
control for cooling-only or
heating-only applications.