7 Parameter level
General Two parameter sets (PAr1 and PAr2) can be stored.
Access
The level can be inhibited.
Applications - Parameter set switching via binary function
v Chapter 8.6 “Binary functions “binF””
- Allocating parameter sets to program segments (only through the setup program)
v
Program editor/Program
Example Setting a 2-state controller with PI action:
Pb1=12°C (proportional band)
rt=160sec (reset time; I component)
dt=0sec (derivative time, D component)