7 Parameter level
30
The parameters Pb2, Cy2, HyS2 and y2 refer to the second controller output for a 3-
state or modulating controller.
The decimal place of some parameters depends on the decimal place setting in the
displays.
PArA PAr1 ( PAr2)
Parameter Display Value range Factory
setting
Meaning
Proportional
band
PB 1 !
0…9999 0 Size of the proportional band
The gain of the controller decreases with
increasing proportional band.
With Pb 1,2 = 0 the controller structure is
ineffective (limit comparator response).
Continuous controllers: Pb1,2 must be >0.
Pb 2
0…9999 0
Derivative time
dt
0…9999 s 80 s Influences the differential component of
the controller output signal
The effect of the D component increases
with increasing derivative time.
Reset time
rt
0…9999 s 350 s Influences the integral component of the
controller output signal
The effect of the I component decreases
with increasing reset time.
Actuator time
tt
5…3000 s 60 s Actuator time range used by the control
valve for modulating controllers.
Cycle time
CY1
0.0…999.9s 20 s With a switched output, the cycle time
should be chosen so that a) the pulsed
energy flow to the process does not cause
any impermissible PV fluctuations and b)
the switching elements are not overloaded.
CY2
0.0…999.9 s 20 s
Contact spacing
db
0.0…999.9 0 The spacing between the two control
contacts for 3-state or modulating
controllers.
Switching
differential
HyS1
0.0…999.9 1 Hysteresis for switching controllers
with Pb1,2 = 0.
HyS2
0.0…999.9 1
Working point
Y0
-100…+100% 0% Output for P and PD controllers
(when x = w then y = Y0).
Output limiting
Y1
0…100% 100% The maximum limit for the output.
Y2
-100…+100 % -100% The minimum limit for the output.
100%
y
xw
HyS1, 2
H
The parameter display on the instrument depends on the controller type
selected.
v Chapter 8.2 “Controller “Cntr””