8 Configuration
36
Procedure
Apply two measurement points ((1), (3)), one after another, to the controller; they
should be as far apart as possible.
At these measurement points, enter the required display value (start value FtS, end
value FtE) in the controller. A reference instrument is most convenient for determining
the measured values M1 and M2.
Measurement conditions must remain stable during programming.
Programming
h Move to measurement point (1)
h Enter start value (2)
1
h Move to measurement point (3)
h Enter end value E (4)
1
To undo fine tuning, the start and end values (FtS, FtE) have to be programmed to the
same value. This automatically sets the start value to 0 and the end value to 1.
Any subsequent fine tuning will otherwise be based on the corrected characteristic.
1. If start value=0 or end value=1 is to be set, then the value must first be altered using I or D to enable
correction.
H
If fine tuning is carried out without a reference instrument, the offset must be
taken into account when moving to measurement point (3).