Analog outputs 0utA Output 5 0ut5
Output 6 0ut6
Output 7 0ut7
Symbol Value/selection Description
Function
Fnct
(analog selector)
switched off
Function of the output
v See “Analog selector” on Page 32.
Type of signal
S iGn
0
1
2
3
0—10V
2—10V
0—20mA
4—20mA
Physical output signal
Range output
r0ut
0101% Signal on going above/below range
101 = last output signal
Zero point
0Pnt
-19990…+9999 A physical output signal is assigned to the value range of an
output variable.
Example:
Setpoint 1 (value range 150 to 500 °C) is to be output via an
analog output (0 — 20mA).
i.e.: 150 to 500°C 0—20mA
Zero point: 150 / End value: 500
End value
End
-1999
100
…+9999
Offset (setup) -19990…+9999 The offset is used to correct the output signal by a certain
amount upwards or downwards.
Examples:
Original Output
value Offset value
294.7 +0.3 295.0
295.3 - 0.3 295.0
Factory settings are shown bold.
If the output is a controller output, the controller
switches over to manual mode and produces the
output level defined under “Controller”.
The setting for rOut is not taken into account.
v Chapter 8.2 “Controller “Cntr””
Setting for controller outputs for cooling.
The following settings have to be defined for
3-state controllers:
Zero point: 0 / End value: -100