8 Configuration
50
Setpoint and
parameter set
switching
A binary function can be used to switch between setpoint 1 and setpoint 2 or
parameter set 1 and parameter set 2.
In order to switch between the four possible setpoints, two binary functions must be
configured to “setpoint switching”. The states of the two binary functions are
designated Z1 and Z2 and switch the setpoints over as shown in the table below:
0 = contact open /OFF 1 = contact closed /ON
Symbol Value/selection Description
Binary input 1
b in1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
no function
Start autotuning
Cancel autotuning
Change to manual mode
Controller off (controller outputs are switched off)
Inhibit manual mode
Hold ramp
Cancel ramp
Setpoint changeover
Parameter set switching
Key inhibit
Level inhibit
Display “off” with key inhibit
Acknowledge limit comparators
Inhibit program start
Start program
Pause program
Cancel program
Segment change
Start timer 1
Start timer 2
Cancel timer 1
Cancel timer 2
Level inhibit:
The parameter and configuration levels are inhibited.
Program end signal:
The signal is active after approx. 1 second (pulse)
Text display:
If the binary function is active, a configurable text is shown in
the lower display. The text can be uniquely defined (only
through the setup program).
Type 703041:
The settings for the binary inputs 1+2 have priority over those
for the logic outputs.
...
Binary input 8
b in8
Limit comparator 1
LC1
...
Limit comparator 4
LC4
Timer 1
tF1
Timer 2
tF2
Logic 1
Lo1
Logic 2
Lo2
Control contact 1
CC1
...
Control contact 4
CC4
Tolerance limit signal
toLS
Program end signal
PrES
Factory settings are shown bold.
Setpoint switching Parameter set switching Binary signal
Setpoint 1 active Parameter set 1 active 0/contact open
Setpoint 2 active Parameter set 2 active 1/contact closed
Setpoint Z2 Z1
Setpoint 1 00
Setpoint 2 01
Setpoint 3 10
Setpoint 4 11