User Manual

8 Configuration
52
8.7 Display “diSP”
Configuration
Analog inputs
Controller
Generator
Limit comparators
Outputs
Binary functions
Display
Timer
Interfaces
Symbol Value/selection Description
General
Upper display
d iSU
(analog selector)
controller process
value
Displayed value for the upper display
v See “Analog selector” on Page 32.
Lower display
d iSL
(analog selector)
controller setpoint
Displayed value for the lower display
v See “Analog selector” on Page 32.
Decimal point
dEcP
0
1
2
no decimal place
one decimal place
two decimal places
If the value that is be displayed can no longer be represented
with the programmed decimal point, then the number of
decimal places will be automatically reduced. If, subsequently,
the measured value decreases, the number increases to the
programmed value of the decimal point.
Brightness
br iG
0…5 (bright) 05 (dark)
16-segment display (setup) switched off
Unit
current segment
current parameter
set
text
Displayed value for the two-digit 16-segment display
Time-out (setup) 030…255s Time period, after which the instrument automatically returns
to normal display if no key is pressed.
Level inhibit (setup) none
configuration level
parameter/
configuration level
operator/
parameter/
configuration level
The access to the individual levels can be inhibited.
User level (setup program)
Up to eight parameters from different levels can be shown under User data (operator level) on
the instrument and edited. The symbols for these parameters (shown in the lower display)
must be assigned by the user himself.
Factory settings are shown bold.