User Manual

8 Configuration
54
8.9 Interfaces “IntF”
Configuration
The interface parameters for the RS422/485 or Profibus-DP interface have to be
configured in order to communicate with PCs, bus systems and peripheral devices.
Configuration
Analog inputs
Controller
Generator
Limit comparators
Outputs
Binary functions
Display
Timer
Interfaces
PROFIBUS-DP Pr0F
Symbol Value/selection Description
Protocol
Prot
0
1
2
Motorola
Intel
Intel integer
Device address
Adr
0…128 255 Address in data network
Analog marker
AnAP
-19990…+9999 Analog value
Binary marker
binP
0 255 Binary value
Factory settings are shown bold.
MODbus r422
Symbol Value/selection Description
Protocol
Prot
0
1
MODbus
MODbus integer
Baud rate
bdrt
0
1
2
9600 bps
19200 bps
38400 bps
Data format
dFt
0
1
2
3
8 data bits, 1 stop bit, no parity
8 data bits, 1 stop bit, odd parity
8 data bits, 1 stop bit, even parity
8 data bits, 2 stop bits, no parity
Device address
Adr
0…1 255 Address in data network
Min. response time (setup) 0500ms Minimum time that elapses between the request of a device in
the data network and the response of the controller.
Factory settings are shown bold.
H
Interface description B70.3041.2