Datasheet

2011-04-14/00506724
Data Sheet 405052 Page 3/11
JUMO GmbH & Co. KG
Delivery address:Mackenrodtstraße 14,
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
e-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
e-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13031, USA
Phone: 315-697-JUMO
1-800-554-JUMO
Fax: 315-697-5867
e-mail: info@jumo.us
Internet: www.jumo.us
Outputs
All analog outputs in 3-wire technology / Switching outputs: open collector, PNP switching
Analog output
Current
Output 475
Output 476
4 - 20 mA and 1 x PNP switching output
0 - 20 mA and 1 x PNP switching output
Voltage
Output 477 0 - 10 V and 1 x PNP switching output
Step response time (analog input)
T90 100 ms
Switching output
Output 470, 475, 476 or 477 1 x PNP switching output
Output 471 2 x PNP switching outputs
Switching type Break contact / make contact
Switching function Window / hysteresis
Switching capacity
Voltage drop from U
B
PNP 2V
Contact rating ON 250 mA / OFF 1mA
Switching cycles > 10 million
Response time 20 ms
Short-circuit proof Yes
Current load check
Pulse period 2 s; T
ON
40 ms
Periodic protective circuit
with overcurrent
f=0.5Hz
Display: Err3 switching output K 1, Err4 switching output K 2
Setting range
Analog output Measuring range scaling (turn down) 1:4
Switching output
Switching point Configurable in the nominal measuring range (> reset point)
Reset point Configurable in the nominal measuring range (< switching point)
Hysteresis Configurable in the nominal measuring range
Input damping 0 - 99.99 s
Input delay 0 - 99.99 s
Burden
Current
4 - 20 mA, three wires
0 - 20 mA, three-wires
RL (U
B
-6.5 V) / 0.022 A (Ω)
RL (U
B
-6.5 V) / 0.022 A (Ω)
Voltage
0 - 10 V DC, three wires RL 10 KΩ