User Manual

7 Commissioning
40
7.12 Setting the reset point (B.RSP)
See section 7.10 "Setting the switching function (B.Fct)", page 37.
Setting range: 0 to 100% of the nominal measuring range
Factory setting: 40% of the nominal measuring range
Setting Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "B.RSP".
"Press"
7.13 Setting the switching difference (hysteresis) (B.HYS)
See section 7.10 "Setting the switching function (B.Fct)", page 37.
Setting range: 0 to 100% of the nominal measuring range
Factory setting: 40% of the nominal measuring range
Setting Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "B.HYS".
"Press"
Enter the value "digit by digit."
"-" Flashing
Continuous
Enter the value "digit by digit."
"-" Flashing
Continuous