7 Commissioning
7.8.1 Setting the starting value of scaling (Sc.Lo)
Setting range: 0 to 75% of the nominal measuring range
Factory setting: Initial value of measuring range
Example The instrument has a nominal measuring range -400 ... +400 mbar
The output signal of the instrument is 0 ...20 mA
Objective: The range from 0 to 200 mbar (customer's measuring
range) will be represented on the output side by
0...20mA.
Setting: The initial value of scaling (Sc.Lo) = 0.000
The final value of scaling (Sc.Hi) = 200.0
Result: At a pressure of less than 0 mbar the instrument reports
an error (value below lower measuring range limit) and
makes the corresponding error signal (0 mA) available at
the output.
At a pressure of 0 mbar the instrument makes 0 mA
available at the output.
At a pressure of +200 mbar the instrument makes 20 mA
available at the output.
At a pressure greater than +200 mbar the instrument
reports an error (measuring range exceeded) and makes
the corresponding error signal (22 mA) available at the
output.
Setting Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "Sc.Lo".
"Press"
The output signal can only be scaled for instruments with
analog output!
Enter the value "digit by digit."
"-" Flashing
Continuous