User Manual

37
5 Operation
5.4.2 Analog output
Parameters Display Setting range
1
1
The standard setting is displayed bold.
Type of signal
(only with analog output)
4to20mA
0to20mA
0to10V
Scaling start
(only with analog output)
-50 °C
Scaling end
(only with analog output)
150 °C/260 °C/500 °C
Note:
Depending on the device ordered.
Error signal
(only with analog output)
3.4 mA or 22 mA
with output signal 4 ... 20 mA
0mA or 22mA
with output signal 0 ... 20 mA
0 V or 10.7 V
with output signal 0 ... 10 V
Chapter 6.10 "Setting the error signal of the
analog output (S.Err)", page 53
Note:
Depending on the configured output signal.